4. Settings
4.1
Example of basic setting
BF 1 FU 63-16
Burner output:
33 kW
Estimated nozzle output:
33 / 11.86*
=
2.78 kg/h
(*
Calorfic value Fuel oil
=
11.86 kWh/kg)
This provides the following nozzle according to the nozzle table, (see Technical
data).
Nozzle:
0.75 Gph
Pump pressure:
10.0 bar
Setting values for 33 kW according to basic setting diagram, (see Technical
data).
Air setting:
=
13.0
Insert setting:
=
7.0
BF 1 FUV 63-16
Burner output:
33 kW
Output increase, for burners with
preheater:
33 x 1.06
=
35 kW
Estimated nozzle output:
35 / 11.86*
=
2.95 kg/h
(*
Calorfic value Fuel oil
=
11.86 kWh/kg)
This provides the following nozzle according to the nozzle table, (see Technical
data).
Nozzle:
0.75 Gph
Pump pressure:
11.0 bar
Setting values for 33 kW according to basic setting diagram, (see Technical
data).
Air setting:
=
13.0
Insert setting:
=
7.0