9.  Fault Location

9.1  Burner will not start

Symptom

Causes

Remedies

Motor starts

Unstable flame

Burner pre-ventilates

Excess air

Adjust the damper 

Low oil pressure

Check the oil pressure

Flame formed

Check the nozzle in relation to the 

combustion apparatus dimensions and 

the ignition electrode position

Burner trips

Incorrect combustion apparatus settings

Check the flame monitor is clean and can 

register light

Motor starts

Flame monitor does not register light

Burner pre-ventilates

Defective flame monitor

Check with using new photocell

No flame formed

Defective oil burner control

Check using new oil burner control (Note: 
replacement of photocell recommended if 

oil burner control replaced)

Burner trips

Check the oil supply to the burner and 

that there are no air bubbles in the pump

No oil

False light

Check function of solenoid

Check flame monitor does not register 

ambient light

No spark

Check high voltage wiring and ignition 

electrodes

Motor does not start

Preheater does not get up to temperature.

Check preheater function

Symptom

Causes

Remedies

Burner does not start

Fuse blown

Check and replace fuse as necessary. 

Investigate cause of fault

Boiler thermostat has not reset

Adjust thermostat

Preheater does not get up to temperature

Check preheater function

Reset the overheating protection. 

Investigate the cause of its deploying.

Remedy fault

Burner pre-ventilates

Overheating protection has deployed

Defective preheater

Check by replacing with new

Defective oil burner control or  

flame monitor

Check that tank, oil lines, solenoid valves, 

pump and nozzle are in good condition

Burner stops

No oil supply

Too great a pressure drop at brake plate

Adjust the burner

Too strong draught prevents flame 

forming

Correct the boiler draught

No spark

Check the ignition transformer. Check the 

ignition electrode settings and ceramics

Preheater temperature too low

Check preheater function

New oil type

Adjust the preheater‘s set operating 

temperature

Check that the oil used has the physical 

parameters that the burner is rated for.  

If not, change the oil.

9.2  Burner will not start after normal use

/1

165 105 09-2    2021-01-21

Содержание 650004465601

Страница 1: ...oviding sustainable energy solutions worldwide CR00445 178 076 66 4 2021 11 15 Installation and maintenance instruction B 55 2 FAME RME LMO24 255C2E E4NC 1069 7P Translation of the original instructio...

Страница 2: ...loaded at www bentone com ecodesign da 1 Manualer p andre sprog 2 www bentone com download eller scan QR koden 3 Indtast br nderens artikelnummer der findes p typeskiltet se billede og v lg dit sprog...

Страница 3: ...22 5 5 Nozzle assembly regulation adjustable brake plate ___ 22 5 6 Hydraulic air adjustment __________________________ 23 5 7 Air setting_______________________________________ 23 6 Maintenance_____...

Страница 4: ...ture 20 to 60 C Check that the burner is compatible with the boiler s output range The label information on the rating plate refers to the burner s minimum and maximum power All components must be ins...

Страница 5: ...e level can exceed 85 dBA Use hearing protection The burner must not be put into operation without proper safety and protection devices Fire extinguisher with Class BE recommended Modifying the design...

Страница 6: ...e burner must be used and then in combination with a suitable oil filter designed for FAME B 100 RME and installed before the burner s oil pump The tank should be cleaned and the water should be check...

Страница 7: ...0 h Motor Twice a year 3 000 h Drive shaft Check replace in the event of damage Check replace in the event of damage Fan wheel Twice a year Replace if need for cleaning imbalance 3 000 h Replace if ne...

Страница 8: ...2 1 Dimensions B 55 2 B 65 2 H I A D E F G B C Type Motor supply Main supply Sound B 55 2 230 400V 3 1 1 8A 230V 0 38A 50Hz 89 dBA 0 5 dBA B 65 2 230 400V 5 9 3 4A 230V 0 38A 50Hz 89 dBA 0 5 dBA Max...

Страница 9: ...0 8 0 100 200 300 400 500 600 700 800 mbar kW 13 0 67 5 kg h 155 800 kW 160302 687 2 1 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 10 0 11 0 12 0 13 0 200 300 400 500 600 700 800 900 1000 1100 1200 mbar...

Страница 10: ...cause of the various boiler types with varying furnace geometries and furnace loads it is impossible to commit to a certain scattering angle or a specific distribution pattern It should be noted that...

Страница 11: ...6 195 5 00 18 62 220 190 19 52 231 199 20 39 242 208 21 22 252 216 5 50 20 48 243 209 21 47 255 219 22 43 266 229 23 34 277 238 6 00 22 34 265 228 23 42 278 239 24 47 290 250 24 46 302 260 6 50 24 20...

Страница 12: ...84 259 223 5 00 22 03 261 225 22 79 270 232 23 55 279 240 24 27 288 247 5 50 24 23 287 247 25 07 297 256 25 91 307 264 26 70 317 272 6 00 26 43 313 270 27 49 326 280 28 27 335 288 29 13 345 297 6 50...

Страница 13: ...Indicating lamp Stage 3 12 Switch ll llll 13 Indicating lamp Stage 2 14 Switch l ll 15 Indicating lamp Stage 1 16 Switch 0 l 17 Motor 18 Adjustment device air damper 19 Scale air regulation 20 Nozzle...

Страница 14: ...former 35 Photocell 36 Ignition wires 37 Air damper 38 Air intake 39 Solenoid valve bloc Stage 2 40 Connecting pipe 41 Solenoid valve 42 Adjustment device Nozzle assembly 43 Nozzle assembly adjustment...

Страница 15: ...ntenance 3 1 1 Installation and maintenance instructions The maintenance instructions supplied with the burner must be kept at an easily accessible location in the boiler room 3 1 2 Instructions The u...

Страница 16: ...16 Bentone 4 Installation 4 1 Handling and lifting instruktion The lifting aid we used here are available as spare parts...

Страница 17: ...eaning filters are recommended for oils of a higher viscosity or oils that contain significant impurities Oil affected parts shall be selected in materials that are capable of withstanding the medium...

Страница 18: ...to reduce radiated heat 9 Install the burner body on the flange 10 Lock the burner body using with the nut nuts 11 Connect the oil pipes to the pump refer to the chapter servicing of burners 12 Connec...

Страница 19: ...Orange cam MV 2 50 Black cam Stage 2 65 Red cam The black cam for Stage 2 MV 2 must be placed between the cams for Stage 1 and Stage 2 The positions of MV 2 are determined by the boiler characteristi...

Страница 20: ...Stage 2 and between Stage 2 and Stage 3 respectively The positions of MV 2 and MV 3 are determined by the boiler characteristics when switching between stages but for a basic setting the cams MV2 and...

Страница 21: ...100 200 300 400 500 600 700 800 160302 035 2 kW Air settings Nozzle assembly Scale Burner output 5 3 Setting values for nozzle assembly and air damper B 65 2 2H 2R 3R 0 10 20 30 40 50 60 70 80 90 100...

Страница 22: ...Stage 1 and Stage 2 by means of a hydraulic piston 3 nozzles Nozzle assembly regulation adjusts the position of the brake plate between Stage 2 and Stage 3 by means of a hydraulic piston Low load The...

Страница 23: ...duce or out to increase The position of the dam per can be read from the damper scale G Carry out flue gas analysis to check the air settings 5 7 Air setting When the burner s power stage has been sel...

Страница 24: ...ecure with the nuts H 10 Open the boiler spectacle flange to access the burner pipe 11 Remove and clean the burner pipe 12 Install the burner pipe make sure you install the drainage hole not on all bu...

Страница 25: ...ubricate the damper shaft if applicable 6 Re engage the damper motor 7 Fit the intake grille over the air intake 8 Slide the burner together and secure it with the nuts H 9 Connect the Eurostecker con...

Страница 26: ...10 Release the damper motor and lock it at 30 11 Fit the mounting plate by guiding the link arm into the attachment point on the air damper and the air damper shaft into the mounting plate make sure...

Страница 27: ...fer the pump coupling to the new pump and adjust to give the same spacing between the pump and pump coupling as before K 6 Fit the oil pump on the burner and tighten the screws J It is important that...

Страница 28: ...ustion Use caution when operating the burner surfaces may be hot Use Loctite 5188 on threaded oil lines If the burner is directly connected ensure that all components on the burner are without power 1...

Страница 29: ...l are 5 0 mm s Check all bolts and nuts for correct torque Check fan wheel for damage and contamination Change when dirty unbalanced Check motor bearings If worn change motor bearings Use lid screw ho...

Страница 30: ...ir dampers and does not normally need to be changed Low load Set control switch for load position to position II high load Turn orange cam disc to 0 to reduce airflow and to 90 to increase airflow Ret...

Страница 31: ...2 s by it being kept hot 7 2 Components 1 Manometer connection G 1 8 2 Connection for nozzle G 1 4 3 Suction line G 1 2 4 Return line G 1 2 5 Pressure regulation with screwdriver 6 Holes Immersion he...

Страница 32: ...nd transports the oil to the valve 6 which controls the oil pressure to the nozzle Oil that does not go through the outlet 7 to the nozzle will be bypassed 2 through the valve 6 back to the return por...

Страница 33: ...33 Bentone 165 305 28 8 Oil burner control 8 1 Wiring diagram B 55 B 65 2 step LMO24 FAME RME...

Страница 34: ...solenoid valve 1 opens 2 2 Solenoid valve 1 opens Oil mist is formed and ignited The photocell indicates a flame The ignition spark goes out after flame indication See Technical data oil burner contro...

Страница 35: ...by pressing and holding the reset button for 3 seconds The number of flashes below is repeated with a pause in between 2 flashes No flame signal when safety time expires 4 flashes False light during s...

Страница 36: ...not start Preheater does not get up to temperature Check preheater function Symptom Causes Remedies Burner does not start Fuse blown Check and replace fuse as necessary Investigate cause of fault Boi...

Страница 37: ...gnition electrodes are not damaged Excessively strong draught Check high voltage cables Check position of nozzle assembly setting Correct boiler draught Excessive pressure drop across the brake plate...

Страница 38: ...too low Check that the oil reaching the pump has the physical parameters that the pump can handle Change the oil or the pump s oil parameters Pump worn Replace the pump Pump run using impure oil that...

Страница 39: ...Address Test performed by Postal address Company name Tel no Boiler Type Make Power kW Bentone Burner Type Model Serial no Fuel Step 1 Step 2 Step 3 Draught in fireplace Fan Press mbar Filter smoke nu...

Страница 40: ...mperature If the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main sw...

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com...

Отзывы: