7

Programming

Using the

KYO320-300-100

application in the

Bentel Security Suite

(rel.5.5.0) pac-

kage.
This paragraph describes the parameters corresponding to the IP Module. For fur-
ther information relating to the installation and operation of the

KYO320-300-100

application in the

Bentel Security Suite

package, programming procedures and

any other parameters not described in this paragraph, please refer to the control unit
INSTRUCTION MANUAL.
The parameters corresponding to the IP Module may be selected and programmed
as described below.
The option

Settings-> Net i/f

in the main menu of

KYO320-300-100

software (Ben-

tel Security Suite) allow you to manage

B-NET

. The programming window will open

(see Figure 1).
The default address assigned to the K-Net should be entered in the

Remote IP ad-

dress

text box: 192.168.0.101. At this point it is possible to connect with the

KNET

P.C.B. and view the settings by pressing the

UpLoad

button.

Check the values listed in the “

Manual settings

” mask, and make any necessary

adjustments in order to align them with the values of the LAN over which the connec-

tion is made. Once the values have been modified, press

Download.

+

Once the following values have been changed: IP_Address, Subnet_Mask and
Gateway1IP, the network Board will only respond to the new configurations.

DHCP

Another way of connecting to the K-NET is to use the DHCP configuration,

which allows an IP address to be assigned to that K-NET automatically. Once DHCP
has been ticked, press the RETURN button. To view the address assigned to the
K-NET automatically, use the procedure described in the View IP address section.
The address viewed using this method will be entered in the Remote IP address box.
Finally, press the

Upload

button.

At this point it will be possible to communicate with the K-NET module and the
KYO320 control unit.

n

Programming Parameters-Network Interface

Remote IP address

The list of general options available for IP Module setup is as

follows:

Ø

IP_Address

– This value is the static IP address assigned to the K-Net module.

Enter the IP address you wish to assign to the IP Module; the network administra-
tor will provide this information alternatively, consult the INSTALLATION
MANUAL and carry out the keypad procedure described in order to read the IP
address (see Viewing the IP Address paragraph). To program the K-Net module
in DHCP mode (dynamic address), the address is 000.000.000.000.
Default value: 192.168.0.101.

Ø

Encrypt Key1

– If it has been programmed, the IP Module will use this key to en-

code and decode the packets exchanged with the PC. The encryption key may
include between 1 and 32 hexadecimal characters. To disable encryption, enter
0 (zero). If the encryption key does not correspond to that of the IP Module, com-
munication between the PC and the IP Module will NOT be permitted.
Enter the encryption key assigned to the IP Module you wish to program.
The default setting is 0 (encryption key not enabled).

Ø

Console Port number

– This is the port which should be used to communicate

with the IP Module. Enter the details of the port assigned to the IP Module you
wish to program (contact the network administrator).
Default value: 3064.

Ø

Installer Code –

This code is used to (remotely or locally) program the IP Module

via the

KYO320-300-100

application in the

Bentel Security Suite

package. The

code should consist of 4 hexadecimal characters. Enter the access code assi-
gned to the IP Module you wish to program.
Default value: 5555.

Connectivity (see Figure 1)

Ø

DHCP

- (see Programming paragraph)

Ø

Manual settings

- (see Programming paragraph)

Ø

IP_Address

-(see Programming paragraph)

Ø

SubNet_Mask –

Must equal the subnet mask for the local subnet. For any single

subnet, there is only one valid submask; all nodes on the same subnet will use
the same subnet mask. The network administrator will provide this information.
Default value: 255.255.0.0.

+

If DHCP is enabled then this section will be ignored.

Ø

Gateway1 IP

– Enter the IP address of the local gateway which may be used by

the IP Module to connect to a PC outside the LAN (WAN).
Default value: 000.000.000.000.

+

If DHCP is enabled then this section will be ignored.

Ø

Ø

DLS Port Number

– This is the port which should be used to communicate with

the control unit.
Default value: 3062.

K-Net Options (vedi Figure 1)

These options are used for various applications.

Set the values only if required by the network administrator, otherwise leave the de-
fault values unchanged.

Ø

Idle Connection Timeout

– Enter the maximum time period during which no

data is transmitted before the connection is terminated.
Default value: 00 (20 seconds).

Ø

Heartbeat Interval

Once Supervision is enabled (see third Screen, Fig. 1), you

will be able to enter a Supervision time value between a minimum of 1 second
and 255 seconds, in steps of 1 second.
Default value: 00 (16 seconds)

Ø

Ethernet Speed

– This option may be used to set the parameters corresponding

to the Ethernet interface of the IP Module. The default value is

Automatic

, where

the Speed and Duplex values are set automatically by the network. If required,
you will find the values to be entered when setting different speeds in the table
below. Default value:

Automatic mode

.

Speed

Data exchange mode (Duplex)

Auto

Auto

10 Mbps

Half

10 Mbps

Full

100 Mbps

Half

100 Mbps

Full

Ø

Output polarity

– This can be used to select the operating mode of the IP Modu-

le OC output. The values which may be set are as follows:

Open on trouble

- The output is suspended when a breakdown occurs (default

setting).

Close on trouble

- The output is connected to the earthing system when a break-

down occurs.

Ø

Output trouble mask

This option can be used to enable and disable indications

from the OC output, for several events recognised by the IP Module:

Network

absent

,

Panel programming

indication is enabled by default.

Default values:

Network absent

.

Ø

Led Trouble Mask

– This option is used to enable or disable the indications pro-

vided by indicator light

L

(

8

), for several events recognised by the IP Module (see

paragraph "Description of the indicator lights" for a description of these events).

Network absent

,

Panel programming

;

Default value: Network absent.

IP Receiver

( see third Screen, Fig. 1)

Ø

Account Code

– The account number is used by the central station to distin-

guish between transmitter. There is one account number programmable for the
K-Net.
Default value: (0000FFFFFF).

+

Account codes 0000FFFFFF,FFFFFFFFFF and 0000000000 are not valid accounts.

Ø

Supervision

– To enable Supervision mode, to tick this option .

Main Receiver

Ø

IP_Address

– Static IP address for the receiver. Program the IP address of the

central station receiver. If a IP receiver is not connected program 0.0.0.0 address.
Default value: 000.000.000.000.

Ø

Receiver1 Local Port

and

Receiver1 Remote Port

– These values show the

ports to communicate with receiver. The same receiver supplies these values.

Default values:3060 (

Receiver1 Local Port

) and 3061 (

Receiver1 Remote Port

).

Backup receiver

Ø

Receiver2 IP

– Static IP address for the second receiver. Program the IP ad-

dress of the second receiver.
Default value: 000.000.000.000.

+

The receiver will be used for backup only; not checked.

Ø

Receiver2 Local Port

and

Receiver2 Remote Port –

These values represent

the ports to be used for communication with the backup receiver.
Default values: 3065 (

Receiver2 Local Port

) and 3066 (

Receiver2 Remote Port

).

+

The receiver will be used for backup only; not checked.

Содержание K-NET

Страница 1: ...9192 BSEC OHSAS 18001 IT 60983 K NET CENTRALE MULTIFUNZIONE ESPANDIBILE EXPANDABLE MULTIFUNCTION CONTROL PANEL CENTRAL MULTIFUNCTI N MODULAR Ó IP MODULE MODULE IP MÓDULO IP MANUALE D INSTALLAZIONE INSTALLATION MANUAL MANUEL D INSTALLATION MANUAL DE INSTALACION MODULO IP CENTRAL BUS MULTIFONCTION ...

Страница 2: ...par du personnel non autorisé L installation du module IP K NET doit être effectuée dans les règles de l art en accord avec les normes en vigueur Le contenu de ce manuel peut être sujet à des modifications sans préavis et n engage aucunement BENTEL SECURITY srl Para programar el Módulo K NET acompañado de estas instrucciones utilizar exclusivamente la aplicación KYO320 300 100 del paquete Bentel S...

Страница 3: ...ogni 5 sec circa della spia L indica il normale funzionamento della scheda Installazione Il Modulo IP va installato sul fondo della centrale come mostrato nella Figura 2 che si trova in fondo alle istruzioni e descritto di seguito Prima d installare il Modulo IP togliere l alimentazione della centrale devo no essere scollegate la rete elettrica e le batterie Se ciò non fosse possibi le collegare p...

Страница 4: ...ornirà questa informazione Valore di default 255 255 0 0 Ignorare questa sezione se è abilitata la modalità DHCP Ø Gateway1 IP Digitare l indirizzo IP del Gateway locale che può essere usato dal modulo IP per collegarsi ad un PC esterno alla rete LAN rete WAN Valore di default 000 000 000 000 Ignorare questa sezione se è abilitata la modalità DHCP DLS Port Number È la porta che deve essere usata p...

Страница 5: ...entrale KYO320 con la scheda di rete presente e confi gurata vedi procedura al paragrafo Prima Programmazione entrati nel menu Installa tore premere A o B per visualizzare la voce PORTE SERIALI seguito dal tasto ENTER Leggere l indirizzo IP e tornare al menu Installatore premendo ESC vedi anche ma nuale Installazione Vol 2 Kyo320 Operazioni da Tastiera solo per utenti esperti dalla finestra di com...

Страница 6: ...The IP Module should be installed to the base of the control unit as illustrated in Fi gure 2 which can be found at the end of the instruction manual Proceed as follows Before installing the IP Module cut the control unit off from its power supply it should be disconnected from the electricity mains and the batte ries If this is not possible do not connect the IP Module power supply un til the ver...

Страница 7: ...ess see Programming paragraph Ø SubNet_Mask Must equal the subnet mask for the local subnet For any single subnet there is only one valid submask all nodes on the same subnet will use the same subnet mask The network administrator will provide this information Default value 255 255 0 0 If DHCP is enabled then this section will be ignored Ø Gateway1 IP Enter the IP address of the local gateway whic...

Страница 8: ...default settings Viewing the IP Address The IP address assigned to the IP Module If the DHCP is configured the current IP address of the KNET circuit board may be checked in 2 ways using a keypad connected to the KYO320 control unit with the network P C B pre sent and configured see procedure in the Initial programming section after ente ring the Installer menu press the A or B buttons to display ...

Страница 9: ...s importante voir la colonne Pr dans le tableau précédent Le clignotement lent environ toutes les 5 secondes du voyant C indique le fonction nement normal de la carte Installation Le Module IP doit être installé sur le fond de la centrale tel qu illustré sur la Figure 2 qui se trouve en bas des instructions et décrit ci dessous Avant d installer le Module IP couper l alimentation de la centrale le...

Страница 10: ... 5555 Connectivité voir Fig 1 Ø Ø DHCP Voir l article Programmation Ø Paramétrage Manuels Voir l article Programmation Ø Adresse IP Voir l article Programmation Ø Sous Masque Réseau Égaler la Subnet mask avec la subnet locale Pour cha que Subnet il existe une seule valeur de Subnet mask tous les noeuds dans la même Subnet utilisent la même Subnet mask L administrateur de réseau fourni ra cette inf...

Страница 11: ...u connecteur 2 Par Software Sur les pages écrans du logiciel voir Fig 1 la touche Défaut est présente Cliquer sur cette touche pour rétablir les réglages par défaut Lecture de l Adresse IP L adresse IP assignée au Module IP Si le DHCP est configuré il est possible de vérifier l IP courant de la carte KNET de 2 façons sur un clavier relié à la centrale KYO320 avec la carte réseau présente et config...

Страница 12: ...del indicador L indica el normal funcio namiento de la tarjeta Instalación El Módulo IP se instala en el fondo de la central como lo muestra la Figura 2 que se encuentra en el fondo de las instrucciones y se describe a continuación Antes de instalar el Módulo IP desconectar la alimentación de la central deben desconectarse la red eléctrica y las baterías Si esto no fuese posi ble conectar al final...

Страница 13: ..._Mask Igualar la máscara de Subred con la subred local Para cada su bred existe sólo un valor de Máscara de subred todos los modos de la misma Subred utilizan la misma Máscara de subred El administrador de red administra rá esta información Valor por defecto 255 255 0 0 Ignorar esta sección si está activado el modo DHCP Ø Gateway1 IP digitar la dirección IP del Gateway local que puede ser utilizad...

Страница 14: ...La dirección IP asignada al Módulo IP Si se ha configurado el DHCP se puede comprobar de dos modos el IP corriente de la tarjeta K Net En un teclado conectado a la central KYO320 con la tarjeta de red presente y con figurada véase procedimiento de Primera Programación una vez que se ha en trado en el menú Instalador presionar las teclas A o B para visualizar el punto PUERTAS SERIALES seguido de la...

Страница 15: ...d binary forms with or without modification are permitted provided that the following conditions are met 1 Redistributions of source code must retain the above copyright notice this list of conditions and the following disclaimer 2 Redistributions in binary form must reproduce the above copyright notice this list of conditions and the following disclaimer in the documentation and or other material...

Страница 16: ...EL SECURITY s r l Via Gabbiano 22 Zona Ind S Scolastica 64013 Corropoli TE ITALY Tel 39 0861 839060 Fax 39 0861 839065 e mail info bentelsecurity com http www bentelsecurity com ISTISBL3KNET 0 2 230310 V10 ...

Отзывы: