Flue / Combustion Air Spigot 

Each heater is fitted with two spigots both of 
which are located to the rear of the appliance  
One of the pair is for connection for the flue 
whilst the other is a screened combustion air 
intake  

WARNING

  

 

(SEE FLUE INSTALLATION 2.5 PAGE 14) 

 

Burner 

The induced draught multi in-shot burner 
assembly is manufactured from aluzinc 
coated steel and mounted to a common steel 
manifold which can be easily withdrawn 
through the burner access compartment. 

Burner Control 

The heaters are fitted with  automatic ignition 
for all models within the range.   
 

Exhaust Fan    

Combustion gases are evacuated to 
atmosphere via an in built power flue venter 
fan which is safety interlocked to the gas 
valve via an air pressure proving device  

Air Movement Fan 

VRABD are supplied with an Axial fan for 
free blowing applications . 
 

Note 

Neither asbestos nor soft soldered joints are 
used in the construction or manufacture of 
the Benson VRA range of Heaters. 
The materials selected for use can withstand 
the mechanical, chemical, and thermal 
stresses which they will be subject to during 
foreseen normal use when installed in 
accordance with the manufacturers 
recommendations.

    

 

 

1.3 General Requirements  

 

Caution

  

Before installation, check that the local 
distribution conditions, nature of gas and 
pressure, and the current state adjustment of 
the appliance are compatible. 
 

Warning

  

Unauthorised modifications to the appliance, 
or departure from the manufacturers   
guidance on intended use, or, installation 

contrary to the manufacturers  
recommendations may constitute a hazard. 
 

Note

  

To ignore the 

warning

 and 

caution

 notices, 

and to ignore the advice from the 
manufacturer on installation, commissioning, 
servicing, or use, will jeopardise any 
applicable warranty, moreover, such a 
situation could also compromise the safe and 
efficient running of the appliance itself, and 
thereby constitute a hazard. 
 
This appliance must be installed by a 
competent person and in accordance with  
European, National, and Local criteria, 
including any relevant standards, codes of 
practice the requirements of the current 
building Regulations (and in particular parts  
J & L), Health and safety regulations IEE 
regulations and any requirements of the local 
Authority, Fire Officer or insurers  
Relevant standards may include BS6230, 
BS6891 and BS5588 parts 2 and 3  
  
Prior to installation the following points 
should be considered; 
 
a)  The position of the heater for the optimum 
efficient distribution and circulation of warm 
air 
 
b)  The position of the heater relative to the 
route of the flue 
 
c)  The position of the heater relative to the 
supply of gas 
 
d)  The position of the heater relative to the 
electrical services, wiring routes, and if 
appropriate, any additional controls. 
 
e)  The position of the heater relative to the 
supply of fresh air 
 
f)  The position of the heater relative to 
potential stratification / circulation problems, 
which generally occur at higher levels and 
which may be overcome through the 
provision of a suitable de-stratification unit. 
 
g)  The position of the heater relative to 
service and maintenance requirements 
 

Содержание variante 2 series

Страница 1: ...DIRECTIONAL NATURAL GAS G20 I2H PROPANE GAS G31 I3P TUBULAR HEATER I N S T A L L A T I O N C O M M I S S I O N I N G S E R V I C I N G U S E R I N S T R U C T I O N S Issue 3 October 2007 THIS MANUAL...

Страница 2: ...ting 8 2 3 Warm Air Circulation 9 2 4 Air Supply 9 2 5 Flue Installation 13 2 6 Electrical Installation 17 2 7 Gas Installation 18 3 0 Commissioning 19 3 1 Electrical Pre tests 19 3 2 Gas pre tests 19...

Страница 3: ...nal connections then we advise that installers consult with gas supplier or provider and satisfy themselves what additional precautions may be necessary Any reference made to Laws Standards Directives...

Страница 4: ...customers with a comprehensive information pack this clearly defines mandatory instructions for the safe installation use and maintenance of the Appliance s Where proprietary items are incorporated in...

Страница 5: ...ced Capital Allowance Scheme 1 1 Certificates of conformity Declarations and Certificates are available upon request from the Quality Control Department at Benson Heating Notified Body PIN Reference i...

Страница 6: ...nufacturers guidance on intended use or installation contrary to the manufacturers recommendations may constitute a hazard Note To ignore the warning and caution notices and to ignore the advice from...

Страница 7: ...anufacturer and is subject to the terms detailed within the Benson Heating conditions of business Note i The warranty may be invalidated if a The warranty registration commissioning card has not been...

Страница 8: ...irculation gas supply electrical supply whilst also providing good and safe working access The heater must be installed so that it is level supports for the heater must be sufficiently robust to withs...

Страница 9: ...joined to the eyebolt at an angle to the vertical and eyebolts if used should be of an approved type 2 3 Warm Air Circulation The air heater should be positioned to enable maximum circulation of disch...

Страница 10: ...air ventilation will be required if The heater s are installed with flue only ie without the positive connection to atmosphere of a combustion air duct And The design air change rate of the heated spa...

Страница 11: ...ce needs to be mechanically ventilated so that the design air change is 0 5 air changes per hour or greater It is a requirement that the mechanical ventilation shall be of the input Type with either n...

Страница 12: ...all height The low level natural ventilation opening should be situated on an external wall and be within 1000 mm of floor level for natural gas and ideally at floor level for l p g gas installations...

Страница 13: ...0 mm The table below provides specific data for each heater model as 2 4 2 4 Natural Ventilation Openings to Enclosures for Flued Heaters Where the heater s is in an enclosure and in flue only mode ie...

Страница 14: ...onnected to the flue system supplied by Benson Heating and be capable of withstanding the stresses and loadings associated with normal use When designing the flue system the prevention of the formatio...

Страница 15: ...33 54 203 33 54 204 33 54 205 Option C12 Not Illustrated Contact Benson Technical Dept In this configuration the heater is connected to a horizontal flue system discharging the products of combustion...

Страница 16: ...L1 maximum flue length 10 metres Universal Terminal Extra pipes to extend the flue are available as an option Pipe 130 x 1000 mm Pipe 130 x 500 mm Pipe 130 x 250 mm Bend 130 x 450 Bend 130 x 900 Part...

Страница 17: ...t is also recommended that BS5854 1980 and BS5440 parts 1 and 2 are used as a consultative document when considering flue requirements If terminating through a wall only use Benson approved horizontal...

Страница 18: ...ng see section 7 1 The correct supply connection points for the live neutral and earth Wiring diagrams are also detailed within this manual section 6 0 The electrical supply isolator should be mounted...

Страница 19: ...nded that screened cable is used when the control is to be sited more than 10 metres away from the heater One electrical panel per heater is required unless heaters are specified for multiple heater c...

Страница 20: ...side the right side panel and is wired in series Operation of either switch will shut down the heater On larger models there will be additional limit stats fitted Caution The power supply to the fan m...

Страница 21: ...tting of the booster Each heater supply must be fitted with a separate isolating cock positioned adjacent to and upstream of the union which must be sited outside the heater The isolating cock should...

Страница 22: ...for the sampling and analysis of the flue gases is accurate to within 0 1 and maintained so that it is regularly calibrated The following pre commissioning checks should be undertaken having first en...

Страница 23: ...t operated No Yes Reset Limit thermostat Air pressure switch made Check flue fan connections Flue fan running Yes Replace flue fan Check flue is clear Change air pressure switch d Yes Spark ignition o...

Страница 24: ...No Bad electrical connection Yes Check wiring connection Reset fan control settings Fan runs in manual mode Fan control settings incorrect Yes Yes Yes Yes Yes No No Faulty fan control Faulty fan motor...

Страница 25: ...Wiring Diagrams VR 250 330 Auto Ignition WARNING NEUTRAL RESET...

Страница 26: ...Wiring Diagram VRBD 410 Auto Ignition WARNING NEUTRAL RESET...

Страница 27: ...TBA Wiring Diagram VRBD 490 Auto Ignition...

Страница 28: ...Wiring Connection CP2 On Off 33 64 350T Wiring Connection CP2 Hi Lo 33 64 488T WARNING NEUTRAL RESET WARNING NEUTRAL RESET...

Страница 29: ...CP4 Controller Connections 33 64 351T Less Controls Connections 33 64 349T WARNING NEUTRAL RESET WARNING NEUTRAL RESET...

Страница 30: ...al Supply 230V 50Hz 1ph Fuse Rating 6 AMP IP Rating IP20 Fan Limit Settings Fan On 50 C Fan Off 30 C Limit 100 C Country Approved Gas Category AT CH CZ DK EE ES FI GB GR HU IE IT IS LT LV NO PT RO SE...

Страница 31: ...n 100 6 7 14 9 14 9 1 15 9 Therefore minimum pre purge time is 286 2 15 9 18 0 seconds The calculation to be conducted is given below for all models Model 250 Minimum pre purge time 286 2 100 CO2 1 Mo...

Страница 32: ...37 5 37 5 2 01 39 51 Therefore minimum pre purge time is 724 7 39 51 18 3 seconds The calculation to be conducted is given below for all models Model 250 Minimum pre purge time 724 7 300 CO2 2 01 Mod...

Страница 33: ...r Ins WG 37 0 14 8 37 0 14 8 37 0 14 8 37 0 14 8 BURNER PRESSURE LPG Mbar Ins WG 25 5 10 2 25 5 10 2 25 5 10 2 25 5 10 2 LPG PROPANE CONSUMPTION m3 hr Kg h 3 21 5 94 4 28 7 92 5 34 9 88 6 41 11 86 MAI...

Страница 34: ...17 33 64 018 33 64 153 33 64 154 Air Pressure Switch 28 40 139 28 40 139 28 40 139 28 40 139 Flue Fan 28 09 089 28 09 089 28 09 090 28 09 090 Run Neon Green 28 50 038 28 50 038 28 50 038 28 50 038 Loc...

Страница 35: ...V2 RABD...

Страница 36: ...Heater A B C D E F G H J K 250 490 225 85 330 900 1630 1860 210 200 130 130 Vertical Co Axial Terminal Dimensions Dimensions in mm s AIR FLUE...

Страница 37: ...ater A B C D E F G B C 250 490 180 420 340 225 200 130 130 750 Horizontal Co Axial Terminal Dimensions Ensure Terminal is located on the wall in this configuration TOP BOTTOM Dimensions in mm s AIR FL...

Страница 38: ...BENSON HEATING LUDLOW ROAD KNIGHTON POWYS LD7 1LP Telephone 44 0 1547 528534 Facsimile 44 0 1547 520399 email information bensonheating co uk Web www bensonheating com...

Отзывы: