background image

1.0 Compliance notices

 

The Benson Variante range of warm air 
heaters detailed herewith are manufactured 
by Benson Heating within a strictly controlled 
environment within the parameters of 
ISO9001: 2000 
These instructions are only valid if the 
following country code is on the appliance 

GB. IE. 

If this code is not present on the 

appliance, it is necessary to refer to the 
technical instructions which will provide the 
necessary information concerning the 
modification of then appliance to the 
conditions of use for the country. 
 
The Benson Variante Range has been  
independently tested and assessed, and has 
been found to meet the Essential  
Requirements of the following European 
Directives. 
 
Gas Appliance Directive (90 / 396 / EEC)  
Machinery Directive (89 / 392 EEC) 
Low Voltage Directive (73 / 23 / EEC & 93 / 
68 / EEC) 
Electromagnetic Compatibility Directive (98 / 
336 / EEC & 91  / 31 / EEC) 
Product Liability Directive 65 / 374 / EEC) 
 
The manufacturer has taken reasonable and 
practical steps to ensure that Benson 
Variante Range of Heaters are safe and 
without risk when properly used. These 
heaters should therefore only be used in the 
manner and purpose for which they were 
intended, and in accordance with the 
recommendations detailed herewith. 
  
The heaters have been designed,  
manufactured, assembled, inspected, and 
tested, with safety and quality in mind, there 
are certain basic precautions which the  
installer and user should be aware of, and 
they are strongly advised to read the  
appropriate sections of the information pack 
accompanying the heater, prior to installation 
or use. 
 
Benson Heating supports all new products 
being supplied to their customers with a  
comprehensive information pack; this clearly 
defines mandatory instructions for the safe 
installation, use, and maintenance, of the  
Appliance (s). 

Where proprietary items are incorporated 
into Benson Heating products, detailed  
information and instructions are also 
 provided as part of the information pack. 
 
It is the responsibility of the installer, owner, 
user, or hirer, of such products supplied by 
Benson Heating, to ensure that they are  
familiar with the appropriate information 
manuals, supplied by the manufacturer, and 
that they are suitably aware of the purpose of 
the manuals and the safety instructions. In 
addition, operators must be suitably trained 
in the use of the appliance so as to ensure its 
continued safe and efficient use. 
 
Benson Heating has a commitment to  
continuous improvement, and therefore  
reserves the right to amend or change the 
specification of the Variante Heater range  
subject to agreement from The Notified 
Body.  
 
Contained within the text of the manual, the 
words '

Caution' 

and 

'Warning'

 are used to 

highlight certain points. 
 

Caution 

is used when failure to follow or 

implement the instruction (s) can lead to 
premature failure or damage to the heater or 
its component parts. 
 

Warning 

is used when failure to heed or 

 implement the instruction (s) can lead to not 
only component damage, but also to a  
hazardous situation being created where 
there is a risk of personal injury. 
 
The Benson Variante range of heaters  
conform to the following European 
Harmonised Standards. 
 
BS EN 1020 Requirements for non domestic 
gas fired forced convection air heaters for 
space heating incorporating a fan to assist 
transportation of combustion air and/ or  
combustion products. 
 
BS EN - ISO 12100-1:2003  & 
BS EN - ISO 12100-2:2003 
Safety of Machinery - Basic Concepts,  
General Principles for Design 
Part 1 &  Part 2 
 

Содержание variante 2 series

Страница 1: ...DIRECTIONAL NATURAL GAS G20 I2H PROPANE GAS G31 I3P TUBULAR HEATER I N S T A L L A T I O N C O M M I S S I O N I N G S E R V I C I N G U S E R I N S T R U C T I O N S Issue 3 October 2007 THIS MANUAL...

Страница 2: ...ting 8 2 3 Warm Air Circulation 9 2 4 Air Supply 9 2 5 Flue Installation 13 2 6 Electrical Installation 17 2 7 Gas Installation 18 3 0 Commissioning 19 3 1 Electrical Pre tests 19 3 2 Gas pre tests 19...

Страница 3: ...nal connections then we advise that installers consult with gas supplier or provider and satisfy themselves what additional precautions may be necessary Any reference made to Laws Standards Directives...

Страница 4: ...customers with a comprehensive information pack this clearly defines mandatory instructions for the safe installation use and maintenance of the Appliance s Where proprietary items are incorporated in...

Страница 5: ...ced Capital Allowance Scheme 1 1 Certificates of conformity Declarations and Certificates are available upon request from the Quality Control Department at Benson Heating Notified Body PIN Reference i...

Страница 6: ...nufacturers guidance on intended use or installation contrary to the manufacturers recommendations may constitute a hazard Note To ignore the warning and caution notices and to ignore the advice from...

Страница 7: ...anufacturer and is subject to the terms detailed within the Benson Heating conditions of business Note i The warranty may be invalidated if a The warranty registration commissioning card has not been...

Страница 8: ...irculation gas supply electrical supply whilst also providing good and safe working access The heater must be installed so that it is level supports for the heater must be sufficiently robust to withs...

Страница 9: ...joined to the eyebolt at an angle to the vertical and eyebolts if used should be of an approved type 2 3 Warm Air Circulation The air heater should be positioned to enable maximum circulation of disch...

Страница 10: ...air ventilation will be required if The heater s are installed with flue only ie without the positive connection to atmosphere of a combustion air duct And The design air change rate of the heated spa...

Страница 11: ...ce needs to be mechanically ventilated so that the design air change is 0 5 air changes per hour or greater It is a requirement that the mechanical ventilation shall be of the input Type with either n...

Страница 12: ...all height The low level natural ventilation opening should be situated on an external wall and be within 1000 mm of floor level for natural gas and ideally at floor level for l p g gas installations...

Страница 13: ...0 mm The table below provides specific data for each heater model as 2 4 2 4 Natural Ventilation Openings to Enclosures for Flued Heaters Where the heater s is in an enclosure and in flue only mode ie...

Страница 14: ...onnected to the flue system supplied by Benson Heating and be capable of withstanding the stresses and loadings associated with normal use When designing the flue system the prevention of the formatio...

Страница 15: ...33 54 203 33 54 204 33 54 205 Option C12 Not Illustrated Contact Benson Technical Dept In this configuration the heater is connected to a horizontal flue system discharging the products of combustion...

Страница 16: ...L1 maximum flue length 10 metres Universal Terminal Extra pipes to extend the flue are available as an option Pipe 130 x 1000 mm Pipe 130 x 500 mm Pipe 130 x 250 mm Bend 130 x 450 Bend 130 x 900 Part...

Страница 17: ...t is also recommended that BS5854 1980 and BS5440 parts 1 and 2 are used as a consultative document when considering flue requirements If terminating through a wall only use Benson approved horizontal...

Страница 18: ...ng see section 7 1 The correct supply connection points for the live neutral and earth Wiring diagrams are also detailed within this manual section 6 0 The electrical supply isolator should be mounted...

Страница 19: ...nded that screened cable is used when the control is to be sited more than 10 metres away from the heater One electrical panel per heater is required unless heaters are specified for multiple heater c...

Страница 20: ...side the right side panel and is wired in series Operation of either switch will shut down the heater On larger models there will be additional limit stats fitted Caution The power supply to the fan m...

Страница 21: ...tting of the booster Each heater supply must be fitted with a separate isolating cock positioned adjacent to and upstream of the union which must be sited outside the heater The isolating cock should...

Страница 22: ...for the sampling and analysis of the flue gases is accurate to within 0 1 and maintained so that it is regularly calibrated The following pre commissioning checks should be undertaken having first en...

Страница 23: ...t operated No Yes Reset Limit thermostat Air pressure switch made Check flue fan connections Flue fan running Yes Replace flue fan Check flue is clear Change air pressure switch d Yes Spark ignition o...

Страница 24: ...No Bad electrical connection Yes Check wiring connection Reset fan control settings Fan runs in manual mode Fan control settings incorrect Yes Yes Yes Yes Yes No No Faulty fan control Faulty fan motor...

Страница 25: ...Wiring Diagrams VR 250 330 Auto Ignition WARNING NEUTRAL RESET...

Страница 26: ...Wiring Diagram VRBD 410 Auto Ignition WARNING NEUTRAL RESET...

Страница 27: ...TBA Wiring Diagram VRBD 490 Auto Ignition...

Страница 28: ...Wiring Connection CP2 On Off 33 64 350T Wiring Connection CP2 Hi Lo 33 64 488T WARNING NEUTRAL RESET WARNING NEUTRAL RESET...

Страница 29: ...CP4 Controller Connections 33 64 351T Less Controls Connections 33 64 349T WARNING NEUTRAL RESET WARNING NEUTRAL RESET...

Страница 30: ...al Supply 230V 50Hz 1ph Fuse Rating 6 AMP IP Rating IP20 Fan Limit Settings Fan On 50 C Fan Off 30 C Limit 100 C Country Approved Gas Category AT CH CZ DK EE ES FI GB GR HU IE IT IS LT LV NO PT RO SE...

Страница 31: ...n 100 6 7 14 9 14 9 1 15 9 Therefore minimum pre purge time is 286 2 15 9 18 0 seconds The calculation to be conducted is given below for all models Model 250 Minimum pre purge time 286 2 100 CO2 1 Mo...

Страница 32: ...37 5 37 5 2 01 39 51 Therefore minimum pre purge time is 724 7 39 51 18 3 seconds The calculation to be conducted is given below for all models Model 250 Minimum pre purge time 724 7 300 CO2 2 01 Mod...

Страница 33: ...r Ins WG 37 0 14 8 37 0 14 8 37 0 14 8 37 0 14 8 BURNER PRESSURE LPG Mbar Ins WG 25 5 10 2 25 5 10 2 25 5 10 2 25 5 10 2 LPG PROPANE CONSUMPTION m3 hr Kg h 3 21 5 94 4 28 7 92 5 34 9 88 6 41 11 86 MAI...

Страница 34: ...17 33 64 018 33 64 153 33 64 154 Air Pressure Switch 28 40 139 28 40 139 28 40 139 28 40 139 Flue Fan 28 09 089 28 09 089 28 09 090 28 09 090 Run Neon Green 28 50 038 28 50 038 28 50 038 28 50 038 Loc...

Страница 35: ...V2 RABD...

Страница 36: ...Heater A B C D E F G H J K 250 490 225 85 330 900 1630 1860 210 200 130 130 Vertical Co Axial Terminal Dimensions Dimensions in mm s AIR FLUE...

Страница 37: ...ater A B C D E F G B C 250 490 180 420 340 225 200 130 130 750 Horizontal Co Axial Terminal Dimensions Ensure Terminal is located on the wall in this configuration TOP BOTTOM Dimensions in mm s AIR FL...

Страница 38: ...BENSON HEATING LUDLOW ROAD KNIGHTON POWYS LD7 1LP Telephone 44 0 1547 528534 Facsimile 44 0 1547 520399 email information bensonheating co uk Web www bensonheating com...