8.0 Fault Finding
Burner
fails to
Run
No Power
No
Demand
Check Isolator
Check Fuses
Check
Controls
Burner Lockout
Fan / Limit
Thermostat
Room
Thermostat
Timer
Heat / Ventilate
Switch
On / Off Switch
Burner
starts
Ignition
sequence
but fails to
light and
Lockout
Occurs
Fuel Feed
Incorrect
Check that the
Oil Pressure is
correct
Check that Head
of Gravity is
Sufficient
Check that the
suction Lift is not
too great (two
pipe system)
Check that the
Bypass Plug is
Present
Fuel / Air
Problem
Check Burner
Air Setting
Bleed System
Air in System
Restricted Fuel
Feed
No Spark
Check
Electrode
Possible Fuel
Contamination
Check Valves,
Fuel Feed, Filter
Nozzle for
Blockages or
Restrictions
Check Control