BENSON OIL UNIT HEATER 

17 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Burner gives a 
sparky flame 

Too Much Air 

Air / Fuel Mix Ratio 

Incorrect 

Fuel Feed 

Restricted 

Adjust Air 

Damper 

Check for Air in 

Fuel Line 

Check Fuel 

Pressure 

Check Nozzle 

Check Filter 

Check Fuel 

Lines 

Check Valves 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Burner 

gives a 

smokey 

flame 

Poor 

Combustion 

Insufficient 

Combustion Air 

Inadequate Flue 

Draught 

Check Oil 

Pressure 

Check Air Damper 

Check Nozzles 

Check if Correctly 

fitted 

Check if Correct 

size 

Check if Damaged 

or Worn 

Check Flue 

Содержание OUHA 100

Страница 1: ...N S T A L L A T I O N C O M M I S S I O N I N G S E R V I C I N G U S E R I N S T R U C T I O N S Issue 3 October 2007 PART NO 33 65 190 THIS MANUAL SHOULD BE LEFT WITH THE END USER TO ENSURE SERVICE...

Страница 2: ...y 5 2 0 Installation 6 2 1 Installation Clearances and Mounting Heights 6 2 2 Heater Mounting 7 2 3 Warm Air Circulation 7 2 4 Air Supply 7 3 0 Fuel Installation 9 4 0 Flue Installation 11 5 0 Electri...

Страница 3: ...part of the information pack It is the responsibility of the installer owner user or hirer of such products supplied by Benson Heating to ensure that they are familiar with the appropriate information...

Страница 4: ...or installation contrary to the manufacturers recommendations may constitute a hazard Note To ignore the warning and caution notices and to ignore the advice from the manufacturer on installation com...

Страница 5: ...s codes of practice or similar standards d Air flow through the heater is not in accordance with the manufacturers technical specifications e Internal wiring on the heater has been tampered with or Un...

Страница 6: ...ective flue system The location must also allow for adequate clearance for the air supply return air circulation oil supply electrical supply whilst also providing good and safe working access Suspend...

Страница 7: ...d obstructions Ensure louvres are adjusted outwards and ensure blades are not resonating The air temperature rise on passing the heat exchanger is typically around 340 C A full and unobstructed return...

Страница 8: ...2 16m3 h per kW of rated heat input Mechanical ventilation systems where fitted must be provided with safety interlocks to prevent heater operation in the event of airflow failure 2 4 2 Heaters insta...

Страница 9: ...of the tank and the fuel feed pipe should extend to not less than 100mm above the bottom of the tank A non return valve with a metal to metal seat should be fitted especially if the return pipe work i...

Страница 10: ...ine terminate over the fuel level a non return valve is essential The return line should terminate within the oil tank at the same level as the suction line in this case a non return valve is not requ...

Страница 11: ...al is not situated in a high pressure area the proximity of buildings and other obstacles which will influence this must be taken into account preferably at the design stage Provision must be made for...

Страница 12: ...rm to the appropriate IEE regulations All heaters are supplied fused and pre wired all must be earthed The Control fuse ratings are detailed on the appliance data plate Warning Ensure that the electri...

Страница 13: ...operational details of the burner supplied with the heater as part of the information package is studied prior to commissioning Time intervals within the ignition sequence will vary slightly from one...

Страница 14: ...inely adjusted to achieve a CO2 reading of 12 5 0 5 All Unit Heaters are test fired and pre commissioned as part of the manufacturing process if however during on site commissioning the data are found...

Страница 15: ...aled and are designed so as to be tamper proof Usually such items do not require servicing and therefore should not be tampered with Failure to comply with this can invalidate any warranty and can als...

Страница 16: ...ails to light and Lockout Occurs Fuel Feed Incorrect Check that the Oil Pressure is correct Check that Head of Gravity is Sufficient Check that the suction Lift is not too great two pipe system Check...

Страница 17: ...Check for Air in Fuel Line Check Fuel Pressure Check Nozzle Check Filter Check Fuel Lines Check Valves Burner gives a smokey flame Poor Combustion Insufficient Combustion Air Inadequate Flue Draught...

Страница 18: ...Air Flow over the Heat Exchanger Check Fan and Motor Assembly Check for no Loose Contacts Limit Control Incorrectly Set Reset to 100C Check Fan and Motor are Secure Check that Fan is not Blocked or Ch...

Страница 19: ...BENSON OIL UNIT HEATER 19 9 0 Wiring Diagram OUHA 100 OUHA 140 ON OFF 33 65 100...

Страница 20: ...BENSON OIL UNIT HEATER 20 Wiring Diagram OUHA 200 OUHA 350 ON OFF 33 65 106...

Страница 21: ...BENSON OIL UNIT HEATER 21 Wiring Diagram OUHA 100 OUHA 140 HIGH LOW 33 65 107...

Страница 22: ...BENSON OIL UNIT HEATER 22 Wiring Diagram OUHA 200 OUHA 350 HIGH LOW 33 65 108...

Страница 23: ...BENSON OIL UNIT HEATER 23 Wiring Diagram OUHC 200 OUHC 350 ON OFF 33 65 191...

Страница 24: ...BENSON OIL UNIT HEATER 24 Remote Connections CP2OU Controller On Off 33 65 102 CP2OU Controller High Low 33 65 130...

Страница 25: ...BENSON OIL UNIT HEATER 25 Remote Connections Less Controls 33 65 132 Remote Connections CP4 Optimised Control 33 65 131...

Страница 26: ...98 4 45 1 6 7 2 2 0 9 0 2 3 10 4 2 5 11 34 Oil Connection BSP 3 8 3 8 3 8 3 8 3 8 3 8 Air Throw mtrs 21 23 31 37 36 39 Air Flow Axial m3 s ft3 m 0 9 1900 1 02 2120 1 6 3400 1 9 4050 2 44 5180 2 63 55...

Страница 27: ...Holder 20 30 061 20 30 061 20 30 061 20 30 061 20 30 061 20 30 061 Sight Glass Gasket 31 28 084 31 28 084 31 28 084 31 28 084 31 28 084 31 28 084 Fuse 1ph 28 07 049 28 07 049 28 07 049 28 07 049 28 0...

Страница 28: ...BENSON OIL UNIT HEATER 28 12 0 Heater Dimensions Axial Fan...

Страница 29: ...BENSON OIL UNIT HEATER 29 12 1 Heater Dimensions Centrifugal Fan...

Страница 30: ...he instruction s can lead to a premature failure or damage being occasioned to the heater or its component parts Warning is used when failure to heed or implement the instruction s can lead not only t...

Страница 31: ...fan motor will continue to run until heat dissipation allows the fan and limit stat to shut down the fan Caution Do not use the main electrical isolator to turn off the heater to do so can cause dama...

Отзывы: