Keypad Parameters
Keypad parameters related to H2 communication board
-0xFFFF
address. (Hex.)
COM-52 Para Control-2
0006
0x0000
-0xFFFF
Sets up the client’s command
address. (Hex.)
E/M
COM-53 Para Control-3
-
0x0000
-0xFFFF
Sets up the client’s command
address. (Hex.)
E/M
COM-54 Para Control-4
-
0x0000
-0xFFFF
Sets up the client’s command
address. (Hex.)
E/M
COM-55 Para Control-5
-
0x0000
-0xFFFF
Sets up the client’s command
address. (Hex.)
E/M
COM-56 Para Control-6
-
0x0000
-0xFFFF
Sets up the client’s command
address. (Hex.)
E/M
COM-57 Para Control-7
-
0x0000
-0xFFFF
Sets up the
client’s command
address. (Hex.)
E/M
COM-58 Para Control-8
-
0x0000
-0xFFFF
Sets up the client’s command
address. (Hex.)
E/M
COM-94 Comm Update
0
0: NO
1: YES
Update keypad parameters
related to network
communication.
E/M
PRT-12
Note 1
Lost Cmd
Mode
None
0: None
1: Free-Run
2: Dec
3: Hold Input
4: Hold Output
5: Lost Preset
Set the inverter operation for
when a Lost Command has
occurred. (Note1)
E/M
PRT-13 Lost Cmd Time
1.0
0.1
– 120
Lost Command trigger time
E/M
PRT-14
Lost Preset F
0.00
0.05
– 60.00 Sets the Lost Preset speed
E/M
Note 1: PRT-12, Lost Command Mode
Set value
Function
"None"
Maintains the previous status.
"Free-Run"
Lost Command Trip occurs and a free run stop is made.
"Dec"
Lost Command Trip occurs and a deceleration stop is made.
"Hold Input"
Lost Command Warning occurs and the inverter operates with the
previous speed reference.
"Hold Output"
Lost Command Warning occurs and the inverter operates with the
previous running speed.
"Lost Preset"
Lost Command Warning occurs and the inverter operates with speed
reference set at PRT-14.