32
890053-03-01
Connecting with Other Products
Fault Code Number
Description
0x2200
OverLoad
0x2310
OverCurrent1
0x2330
GFT
0x2340
OverCurrent2
0x3210
OverVoltage
0x3220
LowVoltage
0x2330
GroundTrip
0x4000
NTCOpen
0x4200
OverHeat
0x5000
FuseOpen
HWDiag
0x7000
FanTrip
0x7120
No Motor Trip
0x7300
EncorderTrip
0x8401
SpeedDevTrip
0x8402
OverSpeed
0x9000
ExternalTrip
BX
Drive Fault Reset
The Drive Fault Reset gives TRIP RESET reference to the inverter when the
setting value changes from 0 to 1 (FALSE to TRUE). Overwriting 1 (TRUE) over
1 (TRUE) does not generate RESET reference for a trip. To allow the EtherNet
communication board to send a RESET command to the inverter when the value
is 1 (TRUE), write 0 (FAULT) first, then write 1 (TRUE) again.
Service
Service code
Definition
Support for class
Support for
instance
0x0E
Get Attribute Single
No
Yes
0x10
Set Attribute Single
No
Yes
④
Inverter Objects (Class 0x2A, Instance 1)
Attribute
Attribute
ID
Access
Attribute
Name
Range
Definition
3
Get
At Reference
0
The output frequency has not
reached the reference frequency.
1
The output frequency has reached