17
Description of Keypad Parameters
⑦
[COM-30] ParaStatus Num: Number of transmission data
You can set COM-23 (opt para-14) to change the number of transmission data
to between
“0” and “8”. The communication board can transmit up to 8 pieces
of data. You can configure the address of the transmission data with
parameters COM-31 through COM-38.
COM-30 Displayed only when Comm Update (COM-94:Yes) is performed after
setting the opt para-14 value to 4 or more.
⑧
[COM-31] Para Status1
– [COM38] Para Status8: Transmission data
address settings
After setting the number of transmission data with COM-23, enter the matching
number of data addresses for the data to transmit to the client (originator) with
parameters COM-31 through COM-38.
This parameter setting is not required for Modbus TCP network
communications.
⑨
[CM-50] Para Ctrl Num: Number of Reception data
You can set COM-24 (opt para-15) to change the number of reception data to
between
“0” and “8”. The communication board can receive up to 8 pieces of
data. You can configure the address for the received data with parameters
COM-51 through COM-58.
COM-50 Displayed only when Comm Update (COM-94:Yes) is performed after
setting COM-24 (opt para-15) value to 4 or more.
⑩
[COM-51] Para Control1
– [COM58] Para Control8: Reception data
address settings
After setting the number of reception data with COM-24, enter the matching
number of data addresses for receiving command data from the client
(originator) with parameters COM-51 through COM-58.
This parameter setting is not required for Modbus TCP network
communications.