6
EUROPEAN SPECIFICATI ONS
Power Requirements @ Maximum Flow & Pressure
............................................................... 22 gpm (80 lpm) at 700 RPM with 1 HP Motor (0.75kW)
Maximum Flow Rate
............................................................................................................................................................................................ 80 L/min
Noise Level
................................................................................................................................................................................................................ 72 dB
Maximum Operating Pressure
................................................................................................................................................................................ 3.5 bar
Minimum Pressure
.................................................................................................................................................................................................. 0.7 bar
Maximum Motor Power Requirements
............................................................................................................................................ 1200 watts / 1.2 kW
Bypass Pressure
................................................................................................................................................................................................ Adjustable
Minimum Dry Suction
............................................................................................................................................................................................ 400 mb
Minimum Wet Suction
........................................................................................................................................................................................... 700 mb
Micron Filter (
)
................................................................................................................................................ 10, 35, 70 according to conditions of use
Air Elimination
................................................................................................................................................According to OIML, CEE 77.313 Regulation
Pump Curve
............................................................................................................................................................................................. Refer to Figure 3
INSTALLATION PIPING FOR TYPE 75 PUMP DISPENSER
Refer to the
PEI/RP100,
Recommended Practices for Installation of Underground Liquid Storage
Systems,
PEI/RP200, Recommended Practices for
Installation of Aboveground Liquid Storage Systems,
and all local, state, federal requirements, and accordance’s prior to any installation of all
equipment.
CAUTION
:
THE AIR ELIMINATOR (COPPER) TUBE MUST REMAIN OPEN TO THE ATMOSPHERE FOR PROPER VENTILATION.
To obtain maximum flow rates on a self-contained pump, follow these guidelines.
1.
The total length of horizontal piping between the pump and tank must be no longer than 60 feet.
2.
Static lift on self-contained units must not exceed 10 feet (vertical distance between product level in the storage tank and the center of
the pumping unit).
3.
Use new 1-1/2” galvanized or approved non-metallic pipe for 10-15 GPM pumps. Use new 2” galvanized or approved non-metallic pipe
for 20-24 GPM pumps.
FLEXIBLE CONNECTOR
OR
SWING JOINT (INTERNATIONAL USE)
FIGURE 1
Содержание T-75
Страница 4: ...Bennett T75 Operation Service Parts Manual Table of Contents 2 Page Intentionally Left Blank ...
Страница 13: ...Bennett T75 Operation Service Parts Manual Product Introduction 11 TUBULAR OUTLET MOTOR MOUNT OPTION FIGURE 7 ...
Страница 14: ...Bennett T75 Operation Service Parts Manual Product Introduction 12 SIDE INLET OPTION FIGURE 8 INLET CENTER ...
Страница 16: ...Bennett T75 Operation Service Parts Manual Operation 14 FIGURE 9 ...
Страница 18: ...Bennett T75 Operation Service Parts Manual Operation 16 FIGURE 11 ...
Страница 25: ...Bennett T75 Operation Service Parts Manual 23 Page Intentionally Left Blank ...