Modbus settings
isoNAV685-D_D00215_02_M_XXEN/04.2017
65
0x30CEu
12494
Relay 2
Test
2
Uint16
R/W
1 = Test on
2 = Test off
1…2
0x30CFu
12495
Relay 2
Mode
2
Uint16
R/W
1 = N/O
2 = N/C
1…2
0x30D0u
12496
Relay 2
Function 1
2
Uint16
R/W
see 0x30B7u
1…11
0x30D1u
12497
Relay 2
Function 2
2
Uint16
R/W
see 0x30B7u
1…11
0x30D2u
12498
Relay 2
Function 3
2
Uint16
R/W
see 0x30B7u
1…11
//InsulationAlarm
0x30D3u
12499
Response value 1
4
Uint32
R/W
1,000…
10,000,000
Ω
0x30D5u
12501
Response value 2
4
Uint32
R/W
1,000…
10,000,000
Ω
0x30D7u
12503
Type of mains supply
system
2
Uint16
R/W
1 = 3AC
1
0x30D8u
12504
Profiles
2
Uint16
R/W
1 = Power circuits
2 = Inverter >10Hz
3 = Inverter < 10Hz
1…3
0x30D9u
12505
Coupling monitoring
2
Uint16
R/W
1 = Coupling monitoring on
2 = Coupling monitoring off
1…2
0x30DAu
12506
Coupling devices
2
Uint16
R/W
1 = No coupling device
1
0x30DBu
12507
Fault memory
2
Uint16
R/W
1 = Fault memory on
1
0x30DCu
12508
Start-up delay
2
Uint16
R/W
0…120
s
0x30DDu
12509
Activate/deactivate
device
2
Uint16
R/W
1 = Activates device
2 = Deactivates device
1…2
0x30DE
12510
DC Alarm
2
Uint16
R/W
20…1,000
V
0x30DF
12511
DC Alarm on/off
2
Uint16
R/W
1 = DC Alarm on
2 = DC Alarm off
1…2
Register address
(hexadecimal)
Register
address
(decimal)
Description
Num-
ber
Data type
Mode
Comment
Range
Unit