Modbus settings
isoNAV685-D_D00215_02_M_XXEN/04.2017
57
0x10A0
4256
Channel number (10)
2
Uint16
RO
0x10A1
4257
DC residual voltage
4
Float
RO
V
0x10A3 - 0x10AF
4259-4271
See previous channel
RO
0x10B0
4272
Channel number (11)
2
Uint16
RO
0x10B1
4273
Power frequency
4
Float
RO
0x10B3 - 0x10BF
4275-4287
See previous channel
RO
0x10C0
4288
Channel number (12)
2
Uint16
RO
0x10C1
4289
System connection
4
Float
RO
0 = O.K.
101 = error
0x10C3 - 0x10CF
4291-4303
See previous channel
RO
0x10D0
4304
Channel number (13)
2
Uint16
RO
0x10D1
4305
Connection to earth
4
Float
RO
0 = O.K.
101 = error
0x10D3 - 0x10DF
4307-4319
See previous channel
RO
0x10E0
4320
Channel number (14)
2
Uint16
RO
0x10E1
4321
Device error
4
Float
RO
Device error number
(e.g. 750 -> 7.50 Communication CAN)
0x10E3 - 0x10EF
4323-4335
See previous channel
RO
0x10F0
4336
Channel number (15)
2
Uint16
RO
0x10F1
4337
DC Offset
4
Float
RO
DC shift in the system
0 % = Fault on DC+
100 % = Fault on DC-
0x10F3 - 0x10FF
4339-4351
See previous channel
RO
0x1100
4352
Channel number (16)
2
Uint16
RO
0x1101
4353
Quality of the
measurement
4
Float
RO
Quality of measuring value
0 % = Poor quality
=> change profile
100 % = Good quality
=> Profile fits to the application
0x1103 - 0x110F
4355-4367
See previous channel
RO
0x1110
4368
Channel number (17)
2
Uint16
RO
Register address
(hexadecimal)
Register
address
(decimal)
Description
Num-
ber
Data type
Mode
Comment
Range