8.5 Data-isoGraph
The isoGraph represents the chronological sequence of the insulation resistance over
time. This graphical representation can be displayed over the following time periods:
hour, day, week, month and year.
The measured values for individual representations are stored in a separate memory. Up
to 100 measured values are available to represent each graph. and the resolution of each
graph is determined by these values.
1,0
,100
,010
,001
MΩ
Stunde 16:26 16:52
Data-isoGraph 2
1/4
Change parameter value
Leave view
Modify scale
Modify scale
Change parameter value
Current time scale
8.6 History memory
Up to 1023 alarm messages and device errors are stored in the history memory with date
and time stamp. When the history memory is deleted, the minimum insulation resistance
R
min
will also be reset at Menu/Data Measured values - Data insulation.
History 4.1
Insulation fault
11kΩ
28.03.14
17:02
28.03.14
17:18
8/8
Next message
Leave view
Fault description
Alarm value
Feault occured
Fault disappeared
Previous message
Number of selected
errors/
Total number of
error messages