Modbus settings
isoNAV685-D_D00215_02_M_XXEN/04.2017
59
//ReadOnly
0x2000u
8192
Insulation vaue
4
Float
RO
Ω
0x2002u
8194
Minimum Insulation
value
4
Float
RO
Minimum measured value
Ω
0x2004u
8196
Insulation capacitance
4
Float
RO
F
0x2006u
8198
Voltage L1-L2
4
Float
RO
Voltage measured between phase L1and
phase L2
V
0x2008u
8200
Voltage L1-L3
4
Float
RO
Voltage measured between phase L1and
phase L3
V
0x200Au
8202
Voltage L2-L3
4
Float
RO
Voltage measured between phase L2 and
phase L3
V
0x200C
8204
Voltage L1-PE
4
Float
RO
Voltage measured between L1 and PE
V
0x200E
8206
Voltage L2-PE
4
Float
RO
Voltage measured between L2 and PE
V
0x2010
8208
Voltage L3-PE
4
Float
RO
Voltage measured between L3 and PE
V
0x2012
8210
System frequency
4
Float
RO
Hz
0x2014
8212
System connection
4
Float
RO
101 = Error; 0 = OK
0x2016
8214
Connection to earth
4
Float
RO
101 = Error; 0 = OK
0x2018
8216
Device error
4
Float
RO
Device error number
(e.g. 750 -> 7.50 Communication CAN)
0x201C
8220
DC Offset
4
Float
RO
DC shift in the system
0 % = Fault on DC+
100 % = Fault on DC-
%
0x201E
8222
Quality of measured
value
4
Float
RO
Quality of measuring value
0 % = Poor quality
=> change profile
100 % = Good quality
=> Profile fits the application
%
0x2026
8230
Duration of measuring
pulse
4
Float
RO
0 % = Measuring pulse has switched
100 % = Measuring pulse just before swit-
ching
Register address
(hexadecimal)
Register
address
(decimal)
Description
Num-
ber
Data type
Mode
Comment
Range
Unit