8. Frequently Asked Questions
The ISOMETER® indicates an insulation fault but this fault cannot be located using the
EDS309…. What could cause this problem?
– Individual outgoing circuits in the IT system monitored may be earthed. Check all outgoing
circuits for unintentional earthing.
The N conductor for the transformer that supplies the IT system must also not be earthed.
– There may not be any locating current flowing. Check the earth connection on the locating
current injector PGH18…, IRDH575 for correct connection.
– The PE conductor may have been unintentionally included in the cables in the measuring
clamp or the measuring current transformer.
EDS195P displays the error message "No CT connected". What could cause this problem?
– A measuring clamp is not connected or it is faulty.
– A measuring clamp or a measuring current transformer of the incorrect type has been con-
nected to the EDS195P, see table on page 33.
In case of residual current measurement (I
Δ
n
) the harmonic H… does not appear in the stand-
ard display. What could cause this problem?
– The menu item "2. Settings/ 7. Harmonics:" is not activated.