![Bender EDS3090 Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/bender/eds3090/eds3090_manual_2731604039.webp)
Operation
39
EDS309x_D00012_03_M_XXEN/11.2014
6.11 Menu structure
The menu structure is shown schematically in the following.
Level 1
Level 2
Level 3
or explanation
1. Exit
2. Settings
1. Exit
2. I
Δ
L
ALM: 0.2…10 mA
3. I
Δ
n ALM: 10 mA…10 A
4. Memory: on/off
5. Buzzer: on/off
6. Frequ.: 50/60Hz/up to 1kHz
7. Harmonics: on/off
Response value measured locating current I
Δ
L
Response value residual current I
Δ
n
Audible alarm
Frequency of the system monitored
Indication of harmonics and total harmonic
distortion THD in %
3. System
1. Exit
2. Language
1. Exit
2. German
3. English
4. French
5. Russian
3. Clock
1. Exit
2. Format: D.M.Y
3. Date
4. Time
4. Contrast: 0…15
Contrast setting for display
4. Harmonics
1. Exit
2. H1 < 10 mA
3. H2 < 10 mA
.....
9. H8 < 10 mA
This menu item is used only for the indication
of harmonics from H1 to H8. To display the
harmonic with the greatest amplitude in the
standard display with the menu closed, the
menu item "7. Harmonics: on/off" on the Set-
tings menu is to be activated
5. I
Δ
L
alarms
1. Exit
2. Entries
Alarm No. 001
No. 002
No. ......
3. Delete
1. Exit
2. Delete Data
6. I
Δ
n logger
1. Exit
2. Entries
Entry No. 001
No. 002
No. ......
3. Change: 10…100 %
Percentage change from which logging
becomes active
4. Overwrite: yes/no
Overwrite oldest data record
5. Delete
1. Exit
2. Delete Data
7. Service
For service only
Содержание EDS3090
Страница 6: ...Table of Contents 6 EDS309x_D00012_03_M_XXEN 11 2014...
Страница 26: ...Considerations prior to use 26 EDS309x_D00012_03_M_XXEN 11 2014...
Страница 62: ...Frequently Asked Questions 62 EDS309x_D00012_03_M_XXEN 11 2014...
Страница 65: ......
Страница 66: ......
Страница 67: ......