System description
13
EDS309x_D00012_03_M_XXEN/11.2014
EDS3096PV:
Applicable in PV systems without a locating current injector installed.
Supply voltage for the delivered locating current injector PGH186: AC 50…60 Hz, 230 V.
Insulation fault location, also in IT systems disconnected on all poles or in de-energised IT sys-
tems.
Equipment for insulation fault location in control circuits
Permissible system voltage in the control circuits:
Insulation fault location in IT systems up to AC 42…460 Hz, 20…265 V and DC 20…308 V.
EDS3091:
Can be used in IT systems in which a locating current injector PGH473 or an IRDH575 is already
installed.
EDS3091PG:
Can be used in IT systems in which neither a locating current injector PGH473 nor an IRDH575 is
already installed.
Supply voltage for the locating current generator PGH183 supplied:
AC 50…60 Hz, 230 V
EDS3091PG-13:
Can be used in IT systems in which neither a locating current injector PGH473 nor an IRDH575 is
already installed.
Supply voltage for the locating current generator PGH183-13 supplied:
AC 50…60 Hz, 90…132 V
Equipment for insulation fault location in main circuits and control circuits
EDS3092PG:
Contains the components and combines the features of the EDS3090PG and EDS3091PG
3.1.3
Accessories
You will find information on the standard accessories as well as on optional accessories in the order-
ing data on page 59 and in the component list on page 60.
For series WF… current transformers you will need a BNC to PS2 adapter cable, see page 59.
Only use the components supplied by us on working with the EDS309…. Com-
mercially available measuring clamps are not allowed to be used! This state-
ment also applies to measuring clamps or measuring current transformers from
the Bender range that are not expressly intended to be used with the EDS309….
Along with the measuring clamps supplied, it is allowed to connect to the
EDS195P the following measuring current transformers from the Bender series:
WF…
W… /WR… /WS…
W…-8000/WS…-8000
Series W…AB current transformers can
not
be used!