Web user interface: Settings (via ETH socket)
Server
The password for the web user interface is alphanumeric.
The factory setting is "admin".
•
Administrator (user name admin)
Status (enabled/disabled)
Password (only *** is displayed)
Username (display only)
Write access (display only)
Read access (display only)
•
User (username user)
Status (enabled/disabled)
Password (only *** is displayed)
Username (display only)
Write access (display only)
Read access (display only)
•
Not logged in
Write access (display only)
Read access (display only)
12.9
Buzzer
Setting options
•
Volume (low, normal, high)
•
Mute alarm (off, 1…8 h)
End date (mute alarm): Display of date and time at which the mute is automatically cancelled.
When a mute is set, the LED and header on the device turn blue. A message (e.g. Buzzer off1 h)
and the icon of a crossed-out loudspeaker appear in the device header.
During muting, the system does not meet the normative requirements for audible and visual
alarms.
12.10 Service inspection
Service interval
During the service inspection, the system does not meet the requirements of the standard for
audible and visual alarms.
Service interval
(deactivated, 3 months … 4 years)
Prewarning
(deactivated, 1 week … 3 months) – message before the service interval expires so that plans can
be made for the next inspection.
54
CP305_D00425_00_M_XXEN_09.2022