COMTRAXX® CP305 - Control Panel
Internal device parameters (alarm addresses, test addresses…). Parameters can be set for
individual message texts for each alarm and test address. The CP305 can be used as a master
device in installations with several IT and EDS systems.
The “TEST” button can be used to check the function of the associated devices such as insulation
monitoring devices, LIM (Line Isolation Monitors) and GFCI (Ground Fault Circuit Interrupters).
A message is only sent to the CP305 on which the test was started. The test and its individual
evaluations are carried out sequentially. Finally, a message appears that the test was successful or
an error message will be output.
The CP305 has the following features
•
Display of operating status, warning and alarm messages according to DIN VDE 0100-710,
IEC 60364-7-710 and other standards
•
Plain text display with illuminated 5" touch display
•
Easy to clean and disinfect, degree of protection IP54 (entire device) or IP66 (front glass
pane)
•
Front panel mounted without screws
•
User-friendly, touch-sensitive monitoring system for medical areas and other applications
•
Particularly simple operator guidance
•
Additional information for medical and technical personnel
•
Visual and audible notification in the event of an alarm
•
Clear menu structure
•
Silent due to fan-free operation
•
High-quality display with excellent contrast, high resolution and a wide-viewing angle
•
Device tests and parameter setting changes with minimal service interruptions
•
Standard texts for messages in the national language
•
500 freely programmable alarm messages
•
Bus technology for easy installation and reduced fire load
•
Audible alarm (can be acknowledged or muted)
•
Version for flush mounting and surface mounting
•
Easy putting into service due to predefined alarm text messages
•
History memory with real-time clock to store 1000 warnings and alarms
•
Power supply via power supply unit
•
Parameter setting via Ethernet interface
•
NFC interface for connection to the Bender Connect app
•
Replacing MK2430 (retrofit); other devices on request
Additionally CP305-IO
•
12 digital inputs
•
2 relay contacts (changeover contact)