Technical documentation
Rev. 02
Reactive Factor Controller CX plus
52
605
RESET maximum measured temperature
Yes/No
“
YES
”: Resets the value of the maximum measured temperature. After
confirming the setting with
“YES”
, the RESET takes place. The setting will
automatically return to
“NO”
.
606
RESET alarm messages
Yes/No
“
YES
”: Resets all active alarm messages (display and alarm relay) and the
alarm memory (menu ALARM).
After confirming the setting with
“YES”
, the RESET takes place. The
setting will automatically return to
“NO”
.
NOTE:
The alarm messages on the display are only reset, if the respective
alarms are not active anymore. The alarm relay is only reset, if no alarm is
active anymore.
607
Display of the software version status of the device
-------
For information purposes only. No settings possible.
Software version of the device. This is shown as moving script:
xx.xx.xx
608
Setting of the expert SETUP password (PIN).
0…999
Setting of the expert SETUP password (PIN) for the SETUP menus 200,
300, 400, 500, 600 and 700.
NOTE:
The SETUP menu 100 is always available even without PIN. The
SETUP menu 700 is only available with the option -MB.