Technical documentation
Rev. 02
Reactive Factor Controller CX plus
84
21 Revision list
Date
Name
Revision
Comment
28.06.17
ChP
01
First edition
07.07.17
ARP
02
Revision of the schematic menu screen
22 Annex
22.1 Setting of phase correction angles depending on the connection
Voltage
L1-N
L2-N
L3-N
L1-N
L2-N
L3-N
L1-N
L2-N
L3-N
Current
transformer
L1
L2
L3
L2
L3
L1
L3
L1
L2
Correction angle 0°
0°
0°
240°
240°
240°
120°
120°
120°
Voltage
L2-L3 L3-L1 L1-L2 L2-L3 L3-L1 L1-L2 L2-L3 L3-L1 L1-L2
Current
transformer
L1
L2
L3
L2
L3
L1
L3
L1
L2
Correction angle 90°
90°
90°
330°
330°
330°
210°
210°
210°
22.2 Connection in case of mixed measurement
Vector group
Current transformer
Voltage
Dy5
L1
L2-N
Dy5
L2
N-L3
Dy5
L3
N-L1
Yz5
L1
L2-N
Yz5
L2
N-L3
Yz5
L3
N-L1
Dx6
L1
L3-L2
Dx6
L2
L2-L1
Dx6
L3
L1-L3
Yy6
L1
L3-L2
Yy6
L2
L2-L1
Yy6
L3
L1-L3
Dy11
L1
N-L2
Dy11
L2
L3-N
Dy11
L3
L1-N
Yz11
L1
N-L2
Yz11
L2
L3-N
Yz11
L3
L1-N
Errors excepted and subject to modifications. Beluk GmbH, July 2017