Technical documentation
Rev. 02
Reactive Factor Controller CX plus
31
9.5
Expert SETUP menu CX plus
In order to change from the quick START SETUP menu to the EXPERT SETUP menu of the CX plus,
press the key
or
. You are now requested to enter a PIN. The standard PIN is
242
.
NOTE:
The PIN can be changed in the SETUP menu 608. No matter which PIN was set, you can
always enter the EXPERT
SETUP menu with the master PIN “242”. If the PIN has been set to “000”,
the EXPERT SETUP menu is not protected by a PIN anymore. All SETUP menus are unlocked
without entering a PIN.
Enter the PIN (
242
) and confirm with the key
(
). The previously hidden menus 200 to 700 can
now be selected with the keys
.
You can enter these submenus with the key
(
).
The EXPERT SETUP menu of the CX plus is divided into seven groups. The menu items in these
groups are grouped logically. The following groups exist:
100 Quick START setup
Contains all the important settings for commissioning from the setup menus 200 to 400. This menu is
always visible.
200 Settings MEASUREMENT
Contains settings in order to adjust the measurement of the CX plus to the network conditions.
300 Settings CONTROL
Contains settings in order to adjust the control to the system requirements and to optimise it.
400 Settings STEP DATABASE
The step parameters are set in the step database. When the step identification is switched off, the
step size must be entered manually here for each individual step.