Tofino Xenon Security Appliance Tofino SA
Release 06 09/2018
37
Press the Save/Load/Reset button once.
The SAVE/LOAD LED will illuminate in green. After a few seconds the
MODE, SAVE/LOAD, and RESET LEDs will flash in green in a left to
right sequence to indicate the USB Save is in progress.
When the flashing sequence stops, remove the USB storage device.
If the save was successful the LEDs will revert to the state they were
in prior to the save action.
USB Load
Perform a USB Load to transfer configuration files and firmware updates
stored on a USB storage device to the Tofino SA.
Power on the Tofino SA for at least one minute.
Insert the USB storage device containing the prepared files into the
USB port.
Press the Save/Load/Reset button twice.
The SAVE/LOAD LED will illuminate in yellow. After a few seconds the
MODE, SAVE/LOAD, and RESET LEDs will flash in yellow in a right to
left sequence to indicate the USB Load is in progress.
When the flashing sequence stops, remove the USB storage device.
If the load was successful the FAULT LED will be off.
FAULT LED
The FAULT LED flashes during the USB save and load sequences to
convey specific messages. See the following table to interpret this activity.
No. of
flashes
During save sequence
During load sequence
1
---
The USB port is disabled. In the Tofino
Configurator, check the Communications
setting on the Tofino SA General page. The
method of communication should be "USB
Only" or "Both USB and Network".
2
No USB memory device is connected to
the USB connection, or the file system of
the memory device is not formatted as
FAT or FAT32.
No USB memory device is connected to the
USB connection, or the file system of the
memory device is not formatted as FAT or
FAT32.
3
The device was unable to create any
diagnostic files. Please contact technical
support.
The files on the USB memory device are
invalid.
4
The device was unable to encrypt the
diagnostic files. Please contact technical
support.
The device was unable to decrypt the
configuration files. The files were possibly
damaged during the copying operation.
Repeat the copying operation. If the
condition persists, contact technical support.
Table 12: FAULT LED diagnostics for USB Save and Load