36
Tofino Xenon Security Appliance Tofino SA
Release 06 09/2018
3
Configuration
3.1
Making basic settings
You configure the device using the Tofino Configurator software supplied at
no charge with every device purchased.
Using this software you can configure the Tofino SA in 2 ways:
use an encrypted USB storage device
discover and configure Tofino SA devices over the network (requires the
NetConnect LSM to be loaded in the device)
Regardless of the configuration method used, an IP address is
not
required
for setup. However, when using the network method, both network interfaces
must be connected and the computer running the Tofino Configurator
software must be able to communicate to an IP device on the opposite
interface. For example, if the Tofino Configurator computer is on NET 1 then
another device should be connected in some way on the NET 2 port and the
two devices should be able to ping each other.
You will find further information on discovering, configuring, and managing
the Tofino Xenon Security Appliance in the Tofino Configurator User Manual.
Default settings
Optical 100 Mbit/s ports: 100 Mbit/s full duplex
Twisted pair ports: autonegotiation
Device mode:
Unconfigured mode and passing all traffic
3.1.1
USB interface
The USB port has an interface for the local connection of a USB storage
device. It is used for saving/loading the configuration, transferring event logs,
and updating the firmware and licenses.
Note:
The ACA22-USB storage device has been tested by Tofino Security
and is therefore recommended. You find the order number for the ACA22-
USB, which is available as accessory, under
“Accessories” on page 47
.
USB Save
Perform a USB Save on the Tofino SA to save event log and diagnostic
information from the hardware to a USB storage device.
Power on the Tofino SA for at least one minute.
Insert the USB storage device into the USB port.
Содержание Tofino Xenon
Страница 51: ...Tofino Xenon Security Appliance Tofino SA Release 06 09 2018 51...
Страница 52: ......