Technical description
DRYPOINT RA 200 – 2500 NA
17
5. Technical description
5.1.
Control panel
The control panel illustrated below is the only dryer-operator interface.
K
2
set
DMC 14
°C
esc
°F
1
5
4
3
P
Q
S
0
0
0
9
1
Main switch
4
ON/OFF switch with mains detecting light
2
Electronic control instrument (DMC14)
5
Alarm light
3
Air and refrigerating gas flow diagram
5.2.
Operation
Operating principal
-
The dryer models described in this manual operate all on the same principal. The hot moisture laden air
enters an air to air heat exchanger. The air then goes through the evaporator, also known as the air to refrigerant heat
exchanger. The temperature of the air is reduced to approximately 36°F (2°C), causing water vapor to c ondense to liquid. The
liquid is continuously coalesced and collected in the separator for removal by the condensate drain. The cool moisture free air
then passes back through the air to air heat exchanger to be reheated to within 15 degrees °F (8 degre es °C) of the incoming
air temperature as it exits the dryer.
Refrigerant circuit
-
Refrigerant gas is cycled through the compressor and exits at high pressure to a condenser
where heat is removed causing the refrigerant to condense to a high-pressure liquid state. The liquid is forced through
a capillary tube where the resulting pressure drop allows the refrigerant to boil off at a predetermined temperature. Low-
pressure liquid refrigerant enters the heat exchanger where heat from the incoming air is transferred causing the
refrigerant to boil; the resulting phase change produces a low pressure, low temperature gas. The low-pressure gas is
returned to the compressor, where it is re-compressed and begins the cycle again. During those periods when the
compressed air load is reduced the excess refrigerant is by-passed automatically back to the compressor via the Hot
Gas By-pass Valve circuit.
Содержание DRYPOINT RA 1000/AC NA
Страница 37: ...List of attachments DRYPOINT RA 200 2500 NA 37 7 2 2 Exploded view DRYPOINT RA 200 350 NA ...
Страница 38: ...List of attachments 38 DRYPOINT RA 200 2500 NA 7 2 3 Exploded view DRYPOINT RA 400 500 NA ...
Страница 39: ...List of attachments DRYPOINT RA 200 2500 NA 39 7 2 4 Exploded view DRYPOINT RA 600 1250 NA ...
Страница 40: ...List of attachments 40 DRYPOINT RA 200 2500 NA 7 2 5 Exploded view DRYPOINT RA1500 2500 NA ...
Страница 51: ...List of attachments DRYPOINT RA 200 2500 NA 51 ...