background image

The  control unit  program provides  the possibility  to silence
the  external  buzzer
,  which  may  be  annoying  during  the
test  phase  or  during  the  prolonged  alarms.
Press  "ENTER"  buttonto    change    ON  -  OFF.
To  move  between  the  lines  press  the  UP  and  DOWN

To  change  the  factory  password  (1234)  with  your  own
password.
Move  with  the  buttons  right  and  left  above  the  desired
number,  press  "ENTER",  f or  ev ery  number  ente red
illuminates  the  number  selected,  up  to  all  four  numbers  are
switched  on.
When  inserted,  the  written  "CONFIRMED"  lights  up.

Save  your  own  password  and  do  not  forget  it,  this  time  to
access  the  programming  of  the  unit  you  have  to  enter  the
new  password.
N.B. 
If you forget  your password, use the  "PUK" number  in
the  warranty  sheet.

Posizionarsi  sulla  scritta  “DATALOGGER”    e  premere  il
pulsante  “ENTER”

Dal  datalogger  si  fa  l’Autodiagnosi  di  tutto  il  sistema
con  rilevazioni  di:
A llarmi,  Av arie,  Diag nosi  d elle   sond e,  Trasmissioni,
Malfunzionamenti,ecc.

>  Memorizzazione  Datalogger  50  episodi

The  control  unit  program  provides
the  possibility  to  silence  the
external  siren
,  which  may  be
annoying  during  the  test  phase  or
during  the  prolonged  alarms.

The  extern  siren  silencing  is  signaled  by  a  red  LED
a)  Illuminated  red  LED,  siren  silenced
b)  LED  off,  operating  siren.
Press  "ENTER"  button  to  change  ON  -  OFF.
To  move  between  the  lines  press  the  UP  and  DOWN

Page  10

Down

UP

Left

Right

ENTER

change  Password
datalogger
print

Silent  siren:  off   

ON

Silent  buzzer:  off   

ON

Advanced  func.

General Functions

External  Siren  Silencing

Silencing  the  Internal  Buzzer

Silent  siren:  off   

ON

Silent  buzzer:  off   

ON

Advanced  func.

Silent  siren:  off   

ON

Silent  buzzer:  off   

ON

Advanced  func.

Continue  to  advanced  features

change  Password

change  Password
datalogger
print

DATALOGGER

To  continue  to  the  Advanced  Functions  menu.
By  positionning  on  the  written  "ADVANCED  FUNC."  and
press  the  "ENTER  "  button

To  move  between  the  lines  press  the  UP  and  DOWN

Indicator to return to the previous page, use "UP" and "DOWN"
keys  and  press  "ENTER"

Indicator to advance to the 

ALARM

 

THRESHOLD

 

SELECTION

 page, use

"UP" and "DOWN" keys and press "ENTER"

Indicator to exit the program, use "UP" and "DOWN" keys and
press "ENTER"

Содержание BXI32

Страница 1: ...sary Self diagnosis of the whole system with detections Alarms faults transmissions malfunctions etc Data Logger storage 50 episodes Ordinary maintenance program Alarms Source Automatic reading of the gas type of each sensor Adjustable alarm level for each sensor Automatic operating range from 20 to 100 LEL Efficiency of the connected sensors Positive Security Function Possibility of inserting Rel...

Страница 2: ...by entering the Password All operation and alarm LEDs read page 3 to find out their functions LED that displays the charge status of Buffer battery Main Power Supply 15 VDC 10 Power demand from 1 2W min to a max of 3W Max 15 DC Secondary power supply via battery Max 2 2 Ah not supplied 12 7 V 10 Battery Charger Max 2 2 Ah controlled Relay Contact Range 10A 250V resistive ALARMS Pre Alarm adjustabl...

Страница 3: ... with a moist cloth Precautions MAINTENANCE The user periodically every 6 months must perform a check of the operation of the control unit by spraying a suitable test gas at the base of the sensors connected until the alarm condition is reached At least once a year make a more accurate check by a specialist technician Disabling the detector must be carried out by qualified personnel Suitable senso...

Страница 4: ... the RESET button 6 Pre Alarm When the red light comes on one of the connected senors detects the gas dispersed in the environment and reached a concentration varying from 8 to 16 of the LEL and closes the contact of the relay 1st THRESHOLD 7 Main Alarm When turns on the red alarm LED one of the sensors has detected a gas concentration of 20 of the LEL and closes the contact of the GENERAL ALARM r...

Страница 5: ...ogram provides to enter a password La Password di fabbrica è 1 2 3 4 The Password can be changed by accessing to Advanced Functions program under General Functions Move with the left button above the required number and press ENTER every asterisk will turn on every number until all four asterisks are switched on If the PassWord is correct it reads Accepted Password If you enter the wrong code you ...

Страница 6: ...thing stationary for three minutes the saving is automatic Down UP Left Right ENTER Detection sensors Input settings Sensors Expansion Card Selection To the controller you can associate the following connections 1 connections up to 32 sensors 2 connections up to 31 sensors and a CARD TX4R 3 connections up to 30 sensors and two CARD TX4R To do this you need to acquire the both the sensors that the ...

Страница 7: ...rst 10 20 scale can be set as desired keeping in mind that the intervention threshold cannot be lower than the pre alarm To be set the second scale needs a set the probe concerned to detect 100 b a password is required to proceed Sensor 01 491940 E T Alarm 20 LEL 20 100 READING PERCENTAGE LEL RANGE SENSOR SET 20 RANGE SENSOR SET 100 The program provides to enter a password La Password di fabbrica ...

Страница 8: ...the function you want to subject to relay 1 FOR EXAMPLE FAULT THRESHOLD ALARM Move with the DOWN button above the word sensors With the ENTER button select the sensor to be subjected to relay 1 Continue as above for both the relays and the remaining functions card TX4R 31 Relay 01 02 03 04 Func not used Sensors 1 32 preallarme allarme avaria ADDRESS RELAY NUMBER EVENT SUBJECT Down UP Left Right EN...

Страница 9: ...E UP AND DOWN BUTTONS TO THE NEXT SELECTION Depending on the type of the system it is possible to choose the need to select the Positive Safety Selection Use the UP and DOWN buttons to select Positive Safety Each time you press ENTER button changes the written ON OFF ON enables the Positive Security function OFF disables the Positive Safety function Once chosen move with the UP and DOWN buttons on...

Страница 10: ...isodi The control unit program provides the possibility to silence the external siren which may be annoying during the test phase or during the prolonged alarms The extern siren silencing is signaled by a red LED a Illuminated red LED siren silenced b LED off operating siren Press ENTER button to change ON OFF To move between the lines press the UP and DOWN Page 10 Down UP Left Right ENTER change ...

Страница 11: ...Sensor replacement E15 S01 17 Central Communication Error E16 S01 Use the UP and DOWN buttons to select the written a Print status press ENTER The current status of the control unit and sensors b Print Datalogger press ENTER All datalogger events Page 11 STAMPA STATO ATTUALE ED EVENTI DEL DATALOGGER EXIT BEINAT BXI32 Ver 1 14 S N Example Serial 0102 Date Hour 31 MAY 17 10 00 Datalogger Event 01 06...

Страница 12: ...agnosis consists in carrying out a check up of operation of the entire system in case of anomalies and if necessary resort to repair Examples of reading E01 CE00 central side communication error E01 SE15 sensor 15 communication error E01 EE31 expansion communication error 31 END To exit the program select Return arrow During the Maintenance period the writing In Maintenance 20m appears on the firs...

Страница 13: ...will be totally reset and starts a new countdown of 90 seconds The control unit is now reset N B be sure of what is done because doing this all the previous settings will be lost Down UP Left Right ENTER Factory Reset Advanced Functions follow Maintenance 00 factory reset Indicator to return to the previous page use UP and DOWN keys and press ENTER Indicator to advance to the ALARM THRESHOLD SELEC...

Страница 14: ...h a degree of IP protection depending on the area to be monitored Kitchens Boiler rooms Laboratory etc choosing one of the Beinat s sensors ranging from IP30 to ATEX vedi pagina 3 Sensors installation and positioning 30 cm Light Gas 30 cm Heavy Gas Average Height Volatile Gas INSTALLATION OF GAS SENSORS It is important to remember that remote sensors should be installed bearing in mind that 1 The ...

Страница 15: ... the ends of the connection terminals If the control unit is supplied without Box check that the voltage 15 VDC is present at the ends of the connection terminals If the Fault yellow LED lights up a First check the fault source from the serial network or from the sensor Communication Error If the fault comes from the serial communication check that the cables have been correctly connected and that...

Страница 16: ...ternal siren BEINAT S N AD012G 31 07 17 10 10 BXI32 ver 1 4 CountDown 03 S2 S1 S30 S29 C31 C32 C B A C B A RS 485 Max 1000 meters N B Close jumper end of line of the last device Codice ASI012 Power supply for 8 sensors 110 230 VAC 15 VDC Note Each sensor absorbs 200 mA PAM NC Reset button Ext Alarm 12 V Powersupply 15 VDC Powersupply 110 230 VAC Block diagram electrical connections ...

Страница 17: ... switches that each device possesses until a maximum of 32 addresses Example to select an address Turn the Switch of tenths until you find the desired tenth For example 1 Turn the Switch of units until you find the desired unit For example 6 In this way you set the address 16 REMEMBER TO INSERT THE END LINE CLOSURE AT THE LAST SENSOR OR CARD Selecting line end Open Close ON 3 2 1 C B A 1 2 3 4 5 6...

Страница 18: ...until you find the desired tenth For example 0 Turn the Switch of units until you find the desired unit For example 6 In this way you will set the address 6 Remember to insert the end of line closure to the last sensor or card Yellow LEDs transmission Power supply 15 VDC Transmission 3 C 2 B 1 A Connection and Addressing of an additional Relay Card CARD TX4R follows Electrical Connections WARNING ...

Страница 19: ...pplies In the RS485 network the masses of the devices must be connected together In the case of devices with power supply connected to earth for example PC the earth and ground connection together can generate problems 1 The total length of the RS485 network must not exceed 1000 meters 2 The minimum distance between two devices must not be less than 1 meter 3 The branch line from the main network ...

Страница 20: ...s of a solenoid valve Normally Closed with Positive Safety Connecting a Solenoid valve with sirens to 12 VDC via a power switcing The power supply should be adequate to the consumption of the components C NC NO C NC NO C NC NO C NC NO 1 2 3 4 5 6 7 8 9 Solenoid valve Prealarm Fault Siren ext NA NC Switching power supply 230 VAC Ph N 12 VDc Electrical connections Connections of a solenoid valve Nor...

Страница 21: ... 0 2 8 0 BEINAT S N AD012G 21 10 15 10 10 BXI ver 1 4 Count Down 90 BXI32 90 mm 45 mm 37 mm 90 mm 45 mm 159 mm Measures and dimensions of the unit in rail DIN Omega 9 modules Measurements and dimensions of the control unit in box IP65 ...

Страница 22: ...istributors etc IMPORTANT The operation test should not be carried out with the gas tap as this does not guarantee a sufficient concentration to activate the general alarm Warning If you have the following symptoms vomiting sleepiness or else go to the closest first aid station and inform the operators that you could have been poisoned by Carbon Monoxide or by an excess or deficiency of oxygen NOT...

Страница 23: ...Page 23 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Sensors n Code Address Location Type of gas Reminder table of the addressed sensors configuration ...

Страница 24: ...points in case you buy a new and similar product local collection points waste collection center local recycling center etc By ensuring this product is disposed of correctly you will help prevent potential negative consequence for the environment and human health which could otherwise be caused by inappropriate waste handing of this product The recycling of materials will help to conserve natural ...

Отзывы: