5
5-65
Pr. 154
Reserved
Pr.155
Compensation Coefficient for Motor Instability
a
Factory Setting: 0.0
Settings 0.1 to 5.0 (recommended setting 2.0)
0.0
Disable
This parameter is used to improve a condition of unstable current in any specific area.
For higher frequencies, you can adjust this parameter to 0.0, and increase the setting
value in Pr.155 for 30HP and above (a setting of 2.0 is recommended).
Pr.156
Communication Response Delay Time
a
Factory Setting: 0
Settings 0 to 200 (x500µs)
This parameter is used to set communication response delay time. If you set Pr. 156 to 1
the communication response delay time will be 1 X 500µs=500µs, set Pr. 156 to 2 the
communication response delay time will be 2 X 500µs=1000µs.
Pr.157
Communication Mode Selection
a
Factory Setting: 1
Settings 0: Delta ASCII
1:
MODBUS
This parameter is to select the communication mode, 0 is the existed Delta ASCII
communication mode, whereas 1 is to select MODBUS mode.
B550
Series
sensorless vector frequency drive
Содержание B550-2001
Страница 1: ...B550 Series Sensorless Vector Frequency Drive Installation Quick Start Manual ...
Страница 2: ......
Страница 6: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 8: ...1 2 1 4 External Parts and Labels B550 Series sensorless vector frequency drive ...
Страница 20: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 26: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 92: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 94: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 100: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 116: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...