5
5-41
Pr.89
Transmission Speed (Baud rate)
Factory Setting: 01
Settings 00 4800
bps
01
9600
bps
02
19200
bps
03
38400
bps
This parameter sets the transmission speed for communication on the RS-485 serial port
Pr.90
Transmission Fault Treatment
Factory Setting: 03
Settings 00 Warn
and
Continue
Operating
01 Warn and RAMP to Stop
02 Warn and COAST to Stop
03
Keep
Operation
without
Warning
Pr.91
Time Out Detection
Factory Setting: 0.0
Settings 0.1 to 120.0 sec
0.0
disable
This parameter is used for ASCII mode. When the over-time detection is enabled, the
separation between characters cannot exceed 500 ms.
Pr.92
Communication Protocol
Factory Setting: 00
Settings
00 Modbus ASCII mode, <7,N,2>
01 Modbus ASCII mode, <7,E,1>
02 Modbus ASCII mode, <7,O,1>
03 Modbus RTU mode, <8,N,2>
04 Modbus RTU mode, <8,E,1>
05 Modbus RTU mode, <8,O,1>
1. Computer Control
Each drive has a built-in RS-485 serial interface, marked (RJ-11 Jack) on the control
terminal block, whose pins are defined as shown:
6
1
1: +15V
2: GND
3: SG-
4: SG+
5: NC
6: for communication
B550
Series
sensorless vector frequency drive
Содержание B550-2001
Страница 1: ...B550 Series Sensorless Vector Frequency Drive Installation Quick Start Manual ...
Страница 2: ......
Страница 6: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 8: ...1 2 1 4 External Parts and Labels B550 Series sensorless vector frequency drive ...
Страница 20: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 26: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 92: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 94: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 100: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 116: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...