5
es
5-7
Freq.
Acceleration/Deceleration characteristics
(1), (2) Disabling S curve
(3), (4) Enabling S curve
Pr.15
Jog Accel / Decel Time
a
Factory Setting: 1.0 sec
Settings 0.1 to 600.0 sec or 0.01 to 600.0 sec
Unit: 0.1 or 0.01 sec
This parameter sets the acceleration or deceleration time for Jog operation.
Pr.16
Jog Frequency
a
Factory Setting: 6.00 Hz
Settings 0.00 to 400.0 Hz
Unit: 0.1 Hz
When the JOG function is activated, the AC drive will accelerate from Minimum Output
Frequency (Pr.08) to Jog Frequency (Pr.16). Drive must be in “stop” status for the
operator to activate the JOG function. Likewise, during Jog operation, other commands
cannot be accepted through the keypad but FORWARD, REVERSE and STOP. The
JOG function can be remotely activated when the Jog terminal is closed, and if the Jog
terminal opens, the AC drive will decelerate from Jog Frequency to zero. The accel /
decel time is entered as Jog Accel / Decel Time (Pr.15). Multi-function Input terminals
(M1-M5) can also be used to initiate the JOG operation if so programmed.
B550
Series
sensorless vector frequency drive
Содержание B550-2001
Страница 1: ...B550 Series Sensorless Vector Frequency Drive Installation Quick Start Manual ...
Страница 2: ......
Страница 6: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 8: ...1 2 1 4 External Parts and Labels B550 Series sensorless vector frequency drive ...
Страница 20: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 26: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 92: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 94: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 100: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 116: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...