5-56
Pr.112
External Terminal Scanning Time
Factory Setting: 01
Settings 01 to 20
Unit: 2msec
This function screens the signal on I/O terminals for CPU malfunctions due to external
transients. A setting of 02, makes the scanning time to be 2 x 2 = 4 msec.
Set Pr.77 to 02 before changing settings in Pr.112.
Pr.113
Restart Method after Fault (oc, ov, BB)
Factory Setting: 01
Settings 00 None
speed
search
01 Continue operation after fault speed search from speed reference
02 Continue operation after fault speed search from Minimum speed
This parameter is used to select the restart method after certain faults.
Pr. 114
Cooling Fan Control
Factory Setting: 02
Settings 00 Fan Off when the drive stop after 1 Min
01 AC Drive Runs and Fan On, AC Drive Stops and Fan Off
02
Always
Run
03
Reserved
Pr. 115
PID Set Point Selection
Factory Setting: 00
Settings 00 Disable
01 Keypad (based on Pr.00 setting)
02 AVI (external 0-10V)
03
ACI
(external
4-20mA)
04
PID
set
point
(Pr.125)
B550
Series
sensorless vector frequency drive
Содержание B550-2001
Страница 1: ...B550 Series Sensorless Vector Frequency Drive Installation Quick Start Manual ...
Страница 2: ......
Страница 6: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 8: ...1 2 1 4 External Parts and Labels B550 Series sensorless vector frequency drive ...
Страница 20: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 26: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 92: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 94: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 100: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...
Страница 116: ...This page intentionally left blank B550 Series sensorless vector frequency drive ...