![Beckhoff KL85 Series Скачать руководство пользователя страница 70](http://html1.mh-extra.com/html/beckhoff/kl85-series/kl85-series_documentation_2719270070.webp)
Data structures of the modules
KL85xx und KL9309
70
Version: 2.1.0
Bit
Name
Description
0
LED C1.1
yellow
1
bin
LED K1.1 lights up yellow
1
LED C1.2
yellow
1
bin
LED K1.2 lights up yellow
...
...
...
6
LED C4.1
yellow
1
bin
LED K4.1 lights up yellow
7
LED C4.2
yellow
1
bin
LED K4.2 lights up yellow
5.2.2
KL8524 - control and status bytes
Channel 1
Process data mode
Control byte 1 in process data mode
Control byte 1 (CB1) is located in the
, and is transmitted from the controller to the
terminal.
Bit
CB1.7
CB1.6
CB1.5
CB1.4
CB1.3
CB1.2
CB1.1
CB1.0
Name
RegAccess
-
-
-
-
-
-
-
Key
Bit
Name
Description
CB1.7
RegAccess 0
bin
Register communication off (process data mode)
CB1.6 - CB1.0
-
0
bin
reserved
Status byte 1 in process data mode
The status byte 1 (SB1) is located in the
and is transmitted from terminal to the controller.
Bit
SB1.7
SB1.6
SB1.5
SB1.4
SB1.3
SB1.2
SB1.1
SB1.0
Name
RegAccess
-
-
-
-
-
-
-
Key
Bit
Name
Description
SB1.7
RegAccess 0
bin
Acknowledgment for process data mode
SB1.6 - SB1.0
-
0
bin
reserved
Register communication
Control byte 1 in register communication
Control byte 1 (CB1) is located in the
, and is transmitted from the controller to the
terminal.
Bit
CB1.7
CB1.6
CB1.5
CB1.4
CB1.3
CB1.2
CB1.1
CB1.0
Name
RegAccess
R/W