Mounting and wiring
KL85xx und KL9309
30
Version: 2.1.0
Mounting
When mounting, observe the information in the chapter entitled
.
1. Ensure that the system is powered down and in a safe state.
2. Install the first bus terminal block, consisting of the fieldbus coupler and the desired Bus Terminals, on
a mounting rail.
Instead of a standard end terminal (KL9010), install an end terminal with RJ45 socket (KL9020) as the
last terminal at the end of the first Bus Terminal block.
3. Mount the first manual operating module.
4. Plug the RJ45 plug of an Ethernet cable into the RJ45 socket of the KL85xx until it audibly engages.
Plug the other RJ45 plug of the Ethernet cable into the RJ45 socket of the KL85xx labelled
IN
until it
audibly engages.
5. Mount the next manual operating module.
6. Plug the RJ45 plug of the Ethernet cable into the RJ45 socket of the KL85xx labelled
OUT
of the pre-
vious manual operating module until it audibly engages.
Plug the other RJ45 plug of the Ethernet cable into the RJ45 socket of the KL85xx labelled
IN
of the
added manual operating module until it audibly engages.
7. Repeat steps 5 and 6 in order to connect further expansion terminal blocks. A maximum of 31 expan-
sion terminal blocks can be connected.
8. Set the
Function Switch
on all Coupler Terminals (KL85xx/KL9050) correctly.
Function Switch
Activate the terminating resistor at the last expansion terminal block of your K-bus extension system by
switching the
Function Switch
on the last Coupler Terminal (KL85xx/KL9050) to the Last position.
WARNING
Correct setting of the
Function Switch
Correct setting of the
Function Switches
of all Coupler Terminals (KL9050) within a K-bus
extension system must be ensured:
The
Function Switch
of all Coupler Terminals (KL85xx/KL9050) to which a continuing Eth-
ernet cable is connected must be set to position
Next
! (see image below)
The
Function Switch
may be set to the Last
position only at the last Coupler Terminal
(KL85xx/KL9050) of the K-bus extension system! (see image below)
All expansion terminal blocks connected after a Coupler Terminal (KL85xx/KL9050), whose
Function Switch is set to position Last, are not included correctly in the process image:
- The inputs of these terminals are not visible in the process image!
- The outputs of these terminals are not controlled by the process image!
Correct setting of the
Function Switches
must also be ensured if Coupler Terminals
(KL85xx/KL9050) are replaced!
Fig. 17: Function Switch
Disassembly
When removing, observe the information in the chapter entitled
.
1. Ensure that the system is powered down and in a safe state.
2. Press the plastic lock of the RJ45 plug and pull it from the socket.