Device parameters
EPI4xxx, ERI4xxx
67
Version: 1.6
Subindex
Name
Flags
Default value
0x000C:0
Device Access Locks
RW
2
0x000C:01
Parameter (write) Access Lock
RW
0
0x000C:02
Data Storage Lock
RW
0
0x000C:03
Local Parameterization Lock
RW
0
0x000C:04
Local User Interface Lock
RW
0
Index
Name
Flags
Default value
0x0010
Vendor Name
RO
Beckhoff Automation GmbH & Co. KG
0x0011
Vendor Text
RO
www.beckhoff.com
0x0012
Product Name
RO
EPI4374-0002
0x0013
Product ID
RO
EPI4374-0002
0x0014
Product Text
RO
2 analog input 2 analog output modules
0x0015
Serial Number
RO
00000000
0x0016
Hardware version
RO
00
0x0017
Firmware version
RO
00
0x0018
Application-Specific Tag
RW
0
Subindex
Name
Flags
Default value
0x0050:0
IO Status
RO
4
0x0050:01
State
RO
0x0000 (0
dec
)
0x0500:02
Status code
RO
0x0000 (0
dec
)
Subindex
Name
Flags
Default value
0x0800:0
AI Settings Ch 1
RW
18
0x0800:01
Enable User Scale
RW
0x00 (0
dec
)
0x0800:02
Presentation
RW
Signed
0x0800:05
Siemens bits
RW
0x00 (0
dec
)
0x0800:06
Enable filter
RW
0x01 (1
dec
)
0x0800:07
Enable Limit 1
RW
0x00 (0
dec
)
0x0800:08
Enable Limit 2
RW
0x00 (0
dec
)
0x0800:0A
Enable User Calibration
RW
0x00 (0
dec
)
0x0800:0B
Enable Vendor Calibration
RW
0x01 (1
dec
)
0x0800:0E
Swap Limit Bits
RW
0x00 (0
dec
)
0x0800:11
User Scale Offset
RW
0x0000 (0
dec
)
0x0800:12
User Scale Gain
RW
0x00010000 (65536
dec
)
0x0800:13
Limit 1
RW
0x0000 (0
dec
)
0x0800:14
Limit 2
RW
0x0000 (0
dec
)
0x0800:15
Filter Settings
RW
50 Hz FIR
0x0800:17
User Calibration Offset
RW
0x0000 (0
dec
)
0x0800:18
User Calibration Gain
RW
0x4000 (16384
dec
)
Subindex
Name
Flags
Default value
0x080E:01
ADC raw value
RO
0x0000 (0
dec
)
Subindex
Name
Flags
Default value
0x080F:0
AI Vendor Data Ch 1
RO
12
0x080F:01
R0 Offset
RO
0x0000 (0
dec
)
0x080F:02
R0 Gain
RO
0x4000 (16384
dec
)
0x080F:03
R1 Offset
RO
0x0000 (0
dec
)
0x080F:04
R1 Gain
RO
0x4000 (16384
dec
)
0x080F:05
R2 Offset
RO
0x0000 (0
dec
)
0x080F:06
R2 Gain
RO
0x4000 (16384
dec
)