Commissioning and configuration
EPI4xxx, ERI4xxx
42
Version: 1.6
1.
Information
This field is for information only; the IODD that was read in is displayed under Device Description.
Furthermore, the VendorID, DeviceID and the IO-Link revision (V1.0 or V1.1) of the IO-Link devices are
displayed. If the device is an IO-Link device V1.1, then the
function is supported.
The following settings can be made in the settings for the IO-Link devices (see figure above):
2.
Start-up checks
This parameter can be used to specify that the Vendor ID and Device ID should be checked when the
IO-Link device starts up.
ð
This avoids errors when exchanging IO-Link devices.
3.
CycleTime
Specifies the cycle time for the IO-Link master
4.
Communication mode
Selection of the mode in which the IO-Link port is to be operated.
ð
“Communication”: Default mode for IO-Link devices
ð
“StdDigIn / StdDigOut”: Mode for non-IO-Link devices, automatically selected if the port is configured
as a
5.
Error Reaction
If the “Set Input Data to 0” field is activated:
ð
input data are set to 0 in case of error
ð
Status display: “Error”
6.
Button "Advanced"
7.
Data Storage
Pay attention to the sensor version:
ð
V1.0 -> data storage is not supported
ð
V1.1 -> data are stored in the parameter
server (preset)
8.
Process Data Format
Adaptation of the process data format
If Field “Use Octet String” is selected
ð
complex data types (process data) are
created as octet strings.
Advantage: simple further processing in the
PLC
9.
Firmware Update of the Beckhoff IO-Link
devices
For a firmware update use the “Download” button.
Observe the description in the documentation of
EPIxxxx boxes in chapter
.