Device parameters
EPI4xxx, ERI4xxx
77
Version: 1.6
Index 0A00 diagnostics
Index
(hex)
Name
Meaning
Data type
Flags
Default
0A00:0
Diagnostics
Maximum subindex
RO
0x02 (2
dec
)
0A00:01
Overtemperature
Overheating of the IO-Link module
BOOLEAN
RW
0x00 (0
dec
)
0A00:02
Short detected
Short circuit on the IO-Link C/Q data line
BOOLEAN
RW
0x00 (0
dec
)
0A00:03
L+ low
Power supply voltage too low (< 18 V)
BOOLEAN
RW
0x00 (0
dec
)
0A00:04
2L+ low
1)
The supply voltage P24 is too low (< 18 V)
BOOLEAN
RW
0x00 (0
dec
)
0A00:05
2L+ stat
1)
The supply voltage P24 is not available
(< 8 V)
BOOLEAN
RW
0x00 (0
dec
)
0A00:06 -
0A00:10
Reserved
-
BOOLEAN
RW
0x00 (0
dec
)
1)
„2L+“ was the original name for „P24” in the IO-Link specification.
Index 3800 Al range settings
Index
(hex)
Name
Meaning
Data type
Flags
Default
3800:0
Al Range Settings
Maximum subindex
RW
0x0A (10
dec
)
3800:01
Input type Ch1
Input signal range for channel 1
0: -10 V...+10 V
1: 0 mA…20 mA
2: 4 mA…20 mA
3: 0 V…10 V
UINT16
RW
0x0000 (0
dec
)
3800:02
Input type Ch2
Input signal range for channel 2 (values see
channel 1)
UINT16
RW
0x0000 (0
dec
)
3800:03
Input type Ch3
Input signal range for channel 3 (values see
channel 1)
UINT16
RW
0x0000 (0
dec
)
3800:04
Input type Ch4
Input signal range for channel 4 (values see
channel 1)
UINT16
RW
0x0000 (0
dec
)