Commissioning and configuration
EP1518-0002
36
Version: 2.4
5.4.2
Operation modes
Operation mode selection
There are three operation modes to choose from:
•
•
•
The setting takes place by selecting the PDOs in the Sync-Manager:
Operation mode
Number of
32-bit coun-
ters
Number of "free"
digital inputs
Properties
2 up/down counters
2
2
Single pulses at the counter inputs are
counted; the Gate input or the software gate
enables the counter; count direction via CoE
1 up/down counters
1
5
8 digital inputs, no
counter
-
8
digital inputs:
Filter for inputs 0 and 4 permanently set to
150 µs.
The filter setting for the other inputs is
configurable by software.
Operation mode set-
tings of the PDOs
0x1600 0x1601 0x1A00 0x1A01 0x1A02 0x1A03 Comments
2 up/down counters
(32-bit)
1
1
1
1
0/1
0/1
2 counters, digital inputs,
diagnosis of Us
1 up/down counters
(32-bit)
1
0
1
0
0/1
0/1
8 digital inputs, no
counter
0
0
0
0
0/1
0/1
digital inputs:
Filter for inputs 0 and 4
permanently set to 150 µs.
The filter setting for the
other inputs is configurable
by software.
The module parameters are set in the CoE objects 0x8000:0 for counter 1, 0x8010:0 for counter 2 and
0x8022:0 for the digital inputs. (integrate links)
The second counter is always active internally
Internally the second counter is always active, so that when switching from one 32-bit counter to
two 32-bit counters the previous incoming pulses were counted in the second counter and saved in
the Counter Value.