![Beckhoff ELX3312 Скачать руководство пользователя страница 77](http://html1.mh-extra.com/html/beckhoff/elx3312/elx3312_operating-manual_2719618077.webp)
Parameterization and programming
ELX3312 and ELX3314
77
Version: 1.3.0
5.9.6
Information and diagnostic data
Index 80nE TC Internal data (for Ch. 1 - 4 (0 ≤ n ≤ 3))
Index
(hex)
Name
Meaning
Data type
Flags Default
80nE:0
TC Internal data
Maximum subindex
UINT8
RO
0x04 (4
dec
)
80nE:01
ADC raw value TC
ADC raw value thermocouple
UINT32
RO
0x00000000 (0
dec
)
80nE:02
ADC raw value CJ
ADC raw value cold junction
UINT32
RO
0x00000000 (0
dec
)
80nE:03
CJ temperature
Cold junction temperature (resolution [1/10]°C)
INT16
RO
0x0000 (0
dec
)
80nE:04
CJ voltage
Cold junction voltage (resolution 1 µV)
INT16
RO
0x0000 (0
dec
)
Index F000 Modular device profile
Index
(hex)
Name
Meaning
Data type
Flags Default
F000:0
Modular device profile
General information for the modular device profile
UINT8
RO
0x02 (2
dec
)
F000:01
Module index distance
Index spacing of the objects of the individual channels
UINT16
RO
0x0010 (16
dec
)
F000:02
Maximum number of
modules
Number of channels
UINT16
RO
0x0004 (4
dec
)
Index F008 Code word
Index
(hex)
Name
Meaning
Data type
Flags Default
F008:0
Code word
currently reserved
UINT32
RW
0x00000000 (0
dec
)
Index F010 Module list (for Ch. 1 - 4 (1 ≤ n ≤ 4))
Index
(hex)
Name
Meaning
Data type
Flags Default
F010:0
Module list
Maximum subindex
UINT32
RW
0x0n (n
dec
)
F010:0n
SubIndex 00n
TC Profile
UINT32
RW
0x0000014A
(330
dec
)
5.9.7
Standard objects (0x1000-0x1FFF)
The standard objects have the same meaning for all EtherCAT slaves.
Index 1000 Device type
Index
(hex)
Name
Meaning
Data type
Flags Default
1000:0
Device type
Device type of the EtherCAT slave: the Lo-Word contains
the CoE profile used (5001). The Hi-Word contains the
module profile according to the modular device profile.
UINT32
RO
[ ]
Index 1008 Device name
Index
(hex)
Name
Meaning
Data type
Flags Default
1008:0
Device name
Device name of the EtherCAT slave
STRING
RO
[ ]
Index 1009 Hardware version
Index
(hex)
Name
Meaning
Data type
Flags Default
1009:0
Hardware version
Hardware version of the EtherCAT slave
STRING
RO
00
Содержание ELX3312
Страница 2: ......
Страница 11: ...Foreword ELX3312 and ELX3314 11 Version 1 3 0 Fig 3 ELX9012 with date code 12174444 BTN 0000b0si and Ex marking...