Parameterization and programming
ELX3312 and ELX3314
76
Version: 1.3.0
5.9.4
Input data
Index 60n0 TC Inputs (for Ch. 1 - 4 (0 ≤ n ≤ 3))
Index
(hex)
Name
Meaning
Data type
Flags Default
60n0:0
TC Inputs
Maximum subindex
UINT8
RO
0x11 (17
dec
)
60n0:01
Underrange
Value below measuring range.
BOOLEAN
RO
0x00 (0
dec
)
60n0:02
Overrange
Measuring range exceeded.
BOOLEAN
RO
0x00 (0
dec
)
60n0:03
Limit 1
Limit value monitoring
0: not activated
1: limit range exceeded
2: limit range undershot
BIT2
RO
0x00 (0
dec
)
60n0:05
Limit 2
Limit value monitoring
0: not activated
1: limit range exceeded
2: limit range undershot
BIT2
RO
0x00 (0
dec
)
60n0:07
Error
The error bit is set if the value is invalid (wire breakage,
overrange, underrange).
BOOLEAN
RO
0x00 (0
dec
)
60n0:0F
TxPDO State
Validity of the data of the associated TxPDO (0 = valid, 1
= invalid).
BOOLEAN
RO
0x00 (0
dec
)
60n0:10
TxPDO Toggle
The TxPDO toggle is toggled by the slave when the data
of the associated TxPDO is updated.
BOOLEAN
RO
0x00 (0
dec
)
60n0:11
Value
Analog input value
INT16
RO
0x0000 (0
dec
)
Index 60n0 TSC Slave Frame Elements (ELX3312-0090: n=2, ELX3312-0090: n=4)
Index
(hex)
Name
Meaning
Data type
Flags Default
60n0:0
Max. subindex
UINT8
RO
0x06 (6
dec
)
60n0:01
TSC__Slave Cmd
reserved
UINT8
RO
0x00 (0
dec
)
60n0:02
TSC__Slave ConnID
reserved
UINT16
RO
0x0000 (0
dec
)
60n0:03
TSC__Slave CRC_0
reserved
UINT16
RO
0x0000 (0
dec
)
60n0:04
TSC__Slave CRC_1
reserved
UINT16
RO
0x0000 (0
dec
)
60n0:05
TSC__Slave CRC_2
reserved
UINT16
RO
0x0000 (0
dec
)
60n0:06
TSC__Slave CRC_3
reserved
UINT16
RO
0x0000 (0
dec
)
5.9.5
Output data
Index 70n0 TC Outputs (for Ch. 1 - 4 (0 ≤ n ≤ 3))
Index
(hex)
Name
Meaning
Data type
Flags Default
70n0:0
TC Outputs
Maximum subindex
UINT8
RO
0x11 (17
dec
)
70n0:11
CJCompensation
Temperature of the cold junction (resolution in 1/10 °C)
(index 0x80n0:0C, comparison via the process data)
INT16
RO
0x0000 (0
dec
)
Index 70n0 TSC Master Frame Elements (ELX3312-0090: n=2, ELX3314-0090: n=4)
Index
(hex)
Name
Meaning
Data type
Flags Default
70n0:0
TSC Master Frame Ele-
ments
Max. subindex
UINT8
RO
0x03 (3
dec
)
70n0:01
TSC__Master Cmd
reserved
UINT8
RO
0x00 (0
dec
)
70n0:02
TSC__Master ConnID
reserved
UINT16
RO
0x0000 (0
dec
)
70n0:03
TSC__Master CRC_0
reserved
UINT16
RO
0x0000 (0
dec
)
Содержание ELX3312
Страница 2: ......
Страница 11: ...Foreword ELX3312 and ELX3314 11 Version 1 3 0 Fig 3 ELX9012 with date code 12174444 BTN 0000b0si and Ex marking...