Technical data for explosion protection
ELX3312-0000, ELX3314-0000
Ex marking
ATEX
II 3 (1) G Ex ec [ia Ga] IIC T4 Gc
II (1) D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
IECEx
Ex ec [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
[Ex ia Ma] I
cFMus
AIS Class I, II, III, Division 1, Groups A thru G
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx/Ex ec [ia Ga] IIC T4 Gc
[AEx/Ex ia Da] IIIC T4
Certificate numbers
IECEx BVS 18.0005X
BVS 18 ATEX E 005 X
FM19US0075X, FM19CA0041X
Power supply
Invariable in connection with ELX9560
Field interfaces
U
O
= 4.94 V
I
O
= 0.5 mA
P
O
= 0.5 mW
Characteristic curve: linear
Reactance (without
consideration of the
simultaneousness)
L
0
C
0
Ex ia I
100 mH
1000 µF
Ex ia IIA
100 mH
1000 µF
Ex ia IIB
100 mH
1000 µF
Ex ia IIC
100 mH
100 µF
Ex ia IIIC 100 mH
1000 µF