![Beckhoff EL6692 Скачать руководство пользователя страница 135](http://html1.mh-extra.com/html/beckhoff/el6692/el6692_documentation_2719607135.webp)
Commissioning
EL6692
135
Version: 3.2
Index 1C33 SM input parameter
Index (hex) Name
Meaning
Data type
Flags
Default
1C33:0
SM input parameter
Synchronization parameters for the inputs
UINT8
RO
0x20 (32
dec
)
1C33:01
Sync mode
Current synchronization mode:
• 0: Free Run
• 1: Synchron with SM 3 Event (no outputs
available)
• 2: DC - Synchron with SYNC0 Event
• 3: DC - Synchron with SYNC1 Event
• 34: Synchron with SM 2 Event (outputs available)
UINT16
RW
0x0000 (0
dec
)
1C33:02
Cycle time
as
UINT32
RW
0x00000000
(0
dec
)
1C33:03
Shift time
Time between SYNC0 event and reading of the inputs (in
ns, only DC mode)
UINT32
RW
0x00000000
(0
dec
)
1C33:04
Sync modes sup-
ported
Supported synchronization modes:
• Bit 0: free run is supported
• Bit 1: Synchronous with SM 2 Event is supported
(outputs available)
• Bit 1: Synchronous with SM 3 Event is supported
(no outputs available)
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 01: input shift through local event
(outputs available)
• Bit 4-5 = 10: input shift with SYNC1 event (no
outputs available)
• Bit 14 = 1: dynamic times (measurement through
)
UINT16
RO
0xC007
(49159
dec
)
1C33:05
Minimum cycle time
as
UINT32
RO
0x00000000
(0
dec
)
1C33:06
Calc and copy time
Time between reading of the inputs and availability of the
inputs for the master (in ns, only DC mode)
UINT32
RO
0x00000000
(0
dec
)
1C33:08
Command
as
UINT16
RW
0x0000 (0
dec
)
1C33:09
Delay time
Time between SYNC1 event and reading of the inputs (in
ns, only DC mode)
UINT32
RO
0x00000000
(0
dec
)
1C33:0B
SM event missed
counter
as
UINT16
RO
0x0000 (0
dec
)
1C33:0C
Cycle exceeded
counter
as
UINT16
RO
0x0000 (0
dec
)
1C33:0D
Shift too short counter as
UINT16
RO
0x0000 (0
dec
)
1C33:20
Sync error
as
BOOLEAN
RO
0x00 (0
dec
)