Fault correction
94
───
Version: 1.0
eXtended Transport System
12.3
SoftDrive object
12.3.1
Error
12.3.1
ID
Message
Cause
Number of the solution
10000
Interpolator Object is missing Damaged TcSoftDrive configuration
within the TwinCAT configuration
1
10000
PositionCtrl Object is missing Damaged TcSoftDrive configuration
within the TwinCAT configuration
1
10000
VelocityCtrl Object is missing Damaged TcSoftDrive configuration
within the TwinCAT configuration
1
10000
Encoder Object is missing
Damaged TcSoftDrive configuration
within the TwinCAT configuration
1
10000
Filter Object is missing
Damaged TcSoftDrive configuration
within the TwinCAT configuration
1
10000
Feedforward Object is miss-
ing
Damaged TcSoftDrive configuration
within the TwinCAT configuration
1
10001
Velocity difference too big for
emergency ramp down
Triggering of an emergency ramp by
TcSoftDrive
Difference between the setpoint and
actual value of the velocity is more
than 250 mm/s
2
3
10001
Emergency ramp takes too
long
Emergency ramp triggered by TcSoft-
Drive requires more time than the time
of 0.5 sec configured in the parameter
"EmergencyRamp"
4
5
10002
Velocity following error -
check setpoint generation &
commutation (actual velocity !
= command velocity)
Different sign to the setpoint velocity
and actual velocity, deviation from one
another by more than the velocity of
1000 mm/s set in the parameter
"CommutationErrorVelocity"
6
7
8
9
10003
New mover re-sort while axis
is enabled
New mover search activated during
the enabling of the axis by the NC
controller
2
10004
New Mover 1 detection while
axis is enabled
New Mover 1 detection started during
the enabling of the axis by the NC
controller
2
10005
HW error occur after Mover 1
detection is started
HW error during running Mover 1 de-
tection
10
10006
Both movements while Mover
1 detection do not fit together
Each mover performs two small
movements during the Mover 1 detec-
tion:
These movements must take place in
different directions
11 12
10007
Time out while Mover 1 de-
tection is running
No ending of the Mover 1 detection
possible within the specified time
13