Error no.
Description of error
Comment / measure
10
LS / SE1 (external test-
ing)
Switch off operating voltage, wait 10 s,
switch operating voltage back on. If the
error message persists:
a) Check setting [M.A2] (external LS test)
with regard to connected light barrier.
b) Check connection of LS transmitter in
accordance with item Safety input SE1
(LS / 1k2 / 8K2 / OSE).
c) If a) and b) are correct, an error pos-
sibly exists in the control unit hardware.
The control unit must be replaced.
The door can be operated in emer-
gency mode.
11
LS / SE2 (external test-
ing)
Switch off operating voltage, wait 10 s,
switch operating voltage back on. If the
error message persists:
a) Check setting [M.A4] (external LS test)
with regard to connected light barrier.
b) Check connection of LS transmitter in
accordance with item Safety input SE2
(LS / 1k2 / 8K2 / OSE).
c) If a) and b) are correct, an error pos-
sibly exists in the control unit hardware.
The control unit must be replaced.
The door can be operated in emer-
gency mode.
20
SE1
The last door operation was stopped via
an SE1 command.
21
SE2
The last door operation was stopped via
an SE2 command.
22
EMERGENCY STOP
The last door operation was stopped via
an EMERGENCY STOP command.
23
Pre-limit switch
The pre-limit switch was actuated without
SE1 being actuated within 2 s.
39