Emergency operation - dead-man
•
If control sensors (1k2 / 8k2 / OSE / LS) at safety inputs SE1 / SE2 are defective,
the control unit can be manually operated in dead-man mode in the OPEN or
CLOSE direction.
•
Emergency operation can be controlled via the OPEN and CLOSE inputs, [Ta.+] /
[Ta.-], and also the membrane keypad.
•
Actuate the control sensor briefly twice in the required travel direction then hold ac-
tuated. The door now travels in dead-man mode.
Disable/enable parametrisation
•
All menu items can be disabled in [M.C7] to prevent readjustment. (recommended)
•
[M.C7] = 00 menu items can be modified (as-delivered condition)
•
[M.C7] = 01 no changes possible
•
Disable/enable parametrisation
∙
Continuously actuate EMERGENCY STOP
∙
Select menu [M.C7] and access menu item with [Ta.M]
∙
Press and hold buttons [Ta.+] and [Ta.-]
∙
You can now toggle between the values 00 and 01 with [Ta.M]
Clock counter
•
The number of previous door movements can be read out as 6 digits in [M.C9].
•
Every start in the OPEN direction is counted.
•
After [M.C9] is selected, a sequence of digits runs down 6 times in the display. This
sequence of digits shows the number of OPEN movements, starting after the rest.
Example: Rest - 00 - 35 - 17 - Rest, etc. corresponds to 3,517 movements in the
OPEN direction.
•
The travel counter cannot be reset or modified (read-only memory).
33