80-4280-10, Rev. 4
Miscellaneous HART-Defined Messages
Message
Description
“Field device has more status
available.”
This is a standard HART-defined message that appears
whenever an alarm or other undesirable status exists. This is the
HART protocol mechanism for displaying the other messages in
this section. If this message is displayed without an additional
message, the status cleared before HART read the additional
status.
“A reset or self-test of the field
device has occurred, or power has
been removed and reapplied.”
This message is presented if the DCM-2 has gone through a
power-up reset sequence since the last communication with
the master. This message is only displayed once after a reset.
“A modification has been made
to the configuration of the field
device.”
This message indicates that the DCM-2 has undergone a
configuration change since the last time the HART master has
reset the change flag. Many HART masters disregard the flag
and do not report this message.
“Field device has malfunctioned
due to a hardware error or failure.”
This message indicates that the continuous built-in self-test
cannot verify the microcomputer is operating properly.
61