80-4280-10, Rev. 4
MAINTENANCE
44
FIGURE 5.
CONTROL END REPLACEMENT
The following procedure describes the steps
required to replace the Control End assembly
using the control end replacement kit part number
12-8065-05 or -15. The kits include the control
end which is comprised of a contactless position
sensor (CPS-4), a limit switch assembly, some
screws and washers, and a control end gasket for
replacement, if necessary.
The replacement control end assembly has
been fully calibrated at the factory. This replace-
ment procedure will return the actuator to a close
approximation of its original calibration. Do not
calibrate the actuator until this procedure is com-
plete, and then only if necessary.
REQUIRED TOOLS
1/2” socket
3/32” hex driver
Torque wrenches
(appropriate for 12 lb-in and 10 lb-ft)
Fine point marker
3/16” flat-tipped screwdriver
WARNING
WARNING
Electrical shock hazard. Disconnect
power before proceeding. Remove
the actuator from line voltage and
disconnect any external power
sources feeding the auxiliary switches.
CAUTION
To prevent electrostatic discharge
damage to the electronics, wear a
grounding strap during this procedure.
PROCEDURE
Remove the old control end assembly:
1. Remove power from the actuator.
2. Remove the control end cover (cylinder shape),
using care not to bend the control shaft or
damage the position-sensing assembly inside.
3. Disconnect the control end assembly electrical
circuits by unplugging the three multi-pin
connectors from the actuator. Two connectors
lead from the switch subassembly and the
other connector leads from the Printed Circuit
board. To disconnect the switch subassembly
connectors, use a 3/16” flat-tipped screwdriver
to press the release tab straight back (see
Figure 5) and pull the plug out of its socket.
The connector leading from the P.C. board
slides off with modest force.
4. Loosen the two outermost setscrews on the
coupling.
Do not
loosen the inner setscrews.
5. Use a fine point marker to note the position of
the control end relative to the actuator body.
Mark the drive’s face immediately adjacent to
the top of the notch (see Figure 6).
6. Loosen (do not remove) the four mounting
clamp button head screws (3/8” long) and
slide the top clamp up over the edge of the
shoulder in the body, immediately above the
stator flange (see Figure 6). Snug one of the
screws to hold the clamp up while replacing
the assembly. Allow the bottom clamp to hang
by the screws.
7. Slide the control end assembly away from the
actuator body until it clears the control end
shaft.
SWITCH ASSEMBLY
SWITCH ASSEMBLY
PIN CONNECTOR
PIN CONNECTOR
PRINTED
CIRCUIT
BOARD
PRINTED
CIRCUIT BOARD
Press tabs straight back to
release connectors
KEEPER
ASSEMBLY
KEEPER
ASSEMBLY
PIN
CONNECTORS
PIN
CONNECTORS
SWITCH CAMS
COUPLING
INNER SETSCREWS (2)
(Do Not Adjust)
OUTER SETSCREWS (2)
NOTE: Tighten the setscrew
on the flat of the shaft first.