![Beck 14-100 Скачать руководство пользователя страница 70](http://html1.mh-extra.com/html/beck/14-100/14-100_instruction-manual_2718148070.webp)
70
80-1403-01, Rev. 3
Beck Configuration Port
Local configuration of the Beck actuator can
be accomplished using Serial commands through
the DCM-3 Serial port.
The Beck Digital Control Module (DCM-3) is
equipped with a Serial interface which allows for
direct communication with a computer. Using a
standard DB9 to USB cable, connect the DCM-3
to the computer using the DCM-3’s DB9 connector
(see below for location) and one of the computer’s
USB ports. Note: If your computer is equipped
with an active COM port, a DB9 to DB9 cable may
be utilized. See below for part numbers of cables
available from Beck.
Once connected, communication can be
established between the DCM-3 and the computer
using a terminal emulation program, such as
HyperTerminal
®
. This method of communication
will allow for configuration, calibration and
verification of drive DCM‑3 settings without the use
of custom software applications.
HyperTerminal
®
Software
HyperTerminal is the standard ASCII terminal
emulation software provided with Microsoft
®
Windows
®
. If using HyperTerminal
®
, the following
instructions will assist in setup. Note that some
variation to these instructions may be necessary
depending on the version of HyperTerminal
®
being
used.
After connecting the DCM-3 to the (Windows®-
based) computer, access HyperTerminal
®
by
clicking first on "Start", then "Programs", then
"Accessories", then "Communications", then
"HyperTerminal". Double-click on the "Hypertrm.
exe" icon to start the program. Once HyperTerminal
®
is running, it is necessary to set up a file with the
proper settings to communicate with the DCM-3.
Proceed as follows:
1. If prompted to install a modem, answer "no".
Proceed to enter a name (e.g., "DCM-3")
and select an icon (any will suffice) in the
"Connection Description" box. Click the "OK"
button.
2. The "Connect to" box should open next. At
the bottom of the box, set the "Connect using"
selection to the appropriate USB (or COM) port
that has been connected to the DCM-3. Click
the "OK" button.
3. The port properties box should open next;
this is where the communication settings are
established. The correct settings are:
a. Bits per second = "1200"
b. Data bits = "8"
c. Parity = "none"
d. Stop bits = "1"
e. Flow control = "none"
4. With the appropriate settings entered from Step
3, above, click "OK". Communications should
now be enabled.
5. Press the "Enter" key twice. "OK" should be
displayed indicating that HyperTerminal
®
is
communicating with the DCM-3.
Hyperterminal
®
is a product of Hilgraeve, Inc.
DB9
CONNECTOR
93°C
200°F
22-501
4
-29
TP2
TP3
DCM-3 SERIAL INTERFACE
Setup
Beck Serial Communications Cables
*Note cables may differ in appearance from depiction.
DB9 to DB9
P/N 20-0511-14
DB9 to USB-A
P/N 20-0511-60
Содержание 14-100
Страница 85: ...85 80 1403 01 Rev 3 17 18 2 1 6 5 8 6 3 4 9 14 15 25 7 16 CONTROL ASSEMBLY AND DRIVE TRAIN...
Страница 87: ...87 80 1403 01 Rev 3 14 15 17 18 2 1 6 5 8 6 3 4 9 14 15 25 7 16 CONTROL ASSEMBLY AND DRIVE TRAIN...
Страница 90: ...90 80 1403 01 Rev 3 NOTES...
Страница 91: ...91 80 1403 01 Rev 3...