![Beck 14-100 Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/beck/14-100/14-100_instruction-manual_2718148039.webp)
39
80-1403-01, Rev. 3
* THIS VALUE CAN BE EDITED
** INDICATES AN ACTION RATHER THAN THE VIEWING OR EDITING
OF A PARAMETER
THIS IS THE MENU DISPLAYED BY THE HART COMMUNICATOR
AT POWER-UP IF COMMUNICATION IS ESTABLISHED
THIS AND OTHER OFFLINE MENUS ARE COMMON TO ALL
HART COMMUNICATOR APPLICATIONS - MANY SUBMENUS EXIST
(1)
(2)
1
BLOCK REFERENCE NUMBERS APPEAR AT THE
UPPER RIGHT CORNER OF EACH BLOCK.
Online
(1)
1 Functions
2 Position
45.4%
3 Demand
45.4%
4 Loop(Dem)
11.29 mA
5 Trq/Thrust
Disabled
6 Temp
73 degF
7 Feedback
11.30 mA
2
Functions
1 Setup Checklist
2 Device Information
3 Configuration
4 Statistics
5 Manual Operation
6 Diagnostics
7 Calibration Trim
3A
Setup Checklist
1 Drive S/N*
2 Drive Dir*
RET Incr
3 Feedback*
Enabled
4 CPS Zero%*
1.000 v
5 PositionUnit*
in
6 MaxTravel*
1.75 in
7 Travel*
1.75 in
8 DemRngLwr*
4.00 mA
9 DemRngUpr*
20.00 mA
Dem Curve*
Linear
•
•
•
Alarm Mask
0xffffffff
4B
General Setup
1 Drive Dir*
RET Incr
2 MaxTravel*
1.75 in
3 Travel*
1.75 in
4 StepSize*
0.100%
5 Stall Time*
300 S
6 StallProt*
Enabled
7 LimitSwitch*
Accept
8 PositionUnit*
in
9 Temperature Unit*
degF
4C
PositionSensrSetup
1 Set Pos 0%**
2 Set Pos 100%**
3 PresCPS V
2.816 v
4 CPS Zero%*
1.000 v
5 CPS Span
4.000 v
6 CPS RngLwr
1.000 v
7 CPS RngUpr
5.000 v
8 Pos S/N*
454
9 Snsr Dir
RET Incr
4D
Demand Setup
1 DemRngLwr *
4.00 mA
2 DemRngUpr *
20.00 mA
3 Dem Curve*
Linear
4 Dem Curve Spcl
5 LOS Mode*
Stay
6 LOS Pos*
50.00 %
7 DemLimLwr*
3.20 mA
8 DemLimUpr
21.00 mA
4E
Feedback Setup
1 FB RngLwr*
4.00 mA
2 FB RngUpr*
20.00 mA
3 Feedback*
Enabled
4 FB Curve*
Linear
4F
Thrust Setup
4G
Op Mode
Follow*
Hold*
RunCW*
RunCCW*
Stay
Stop*
4H
Status
1 LED Status
2 Operating Status
3 Switch Status
4 Local Cntrl Status
5 Line Freq
6 CW Inhibitors
7 CCW Inhibitors
4I
4J
RET Thrust
4K
EXT Thrust
4L
Alarm Setup
1 AlarmPol*
Drops Out
2 Alarm Mask*
4M
RealTimeClock
1 RTC Day*
8
2 RTC Month*
8
3 RTC Year*
2014
4 Hour (24)*
8
5 Minute*
5
4A
Review
(3)
3B
Device Information
1 Tag*
BECK2015
2 Descriptor*
3 Message*
4 Model#
14-109
5 Drive S/N*
6 Instld*
11/05/2015
7 Setup*
11/05/2015
8 Calbrtd*
18/05/2015
9 Review
Poll addr*
0
3C
3D
Statistics
1 Starts
285213
2 Reversals
142606
3 Stalls
0
4 OverThrusts
5 Pk Thrust
6 TotRunTm
32263 S
7 High Temp
135 degF
8 Low Temp
43 degF
3E
3F
Diagnostics
1 Status
2 Tests
3 Retract Thrust
4 Extend Thrust
5 Alarm Setup
6 RealTimeClock
3G
Calibration Trim
1 PresCPS V*
2.816 v
2 Loop(Dem)*
11.29 mA
3 Feedback*
11.29 mA
4 Trq/Thrust*
5A
Dem Curve Spcl
1 DemNode1X
0 %
2 DemNode1Y
0 %
3 DemNode2X
5 %
4 DemNode2Y
5 %
•
•
•
DemNode21X
100 %
DemNode21Y
100 %
5B
LED Status
Status OFF
Reverse
OFF
Forward
OFF
Demand
OFF
Position
OFF
Trq/Thrust
OFF
Stall OFF
Temperature
OFF
FB Open
OFF
Limit OFF
Acknowledge
OFF
5C
Operating Status
Dem <> Limits
OFF
Pos <> Limits
OFF
Temp <> Limits
OFF
Torq <> Lim
OFF
Ovr Torq Stop
OFF
Stalled OFF
Feedback Open
OFF
Switch Block
OFF
Switch Status
LV Lim EXT
OFF
LV Lim RET
OFF
OvrRd EXT
OFF
OvrRd RET
OFF
OvrRd Stop
OFF
HndSw EXT
OFF
HndSw RET
OFF
HndSw AUTO
OFF
5D
5E
Local Cntrl Status
Calibrate
OFF
Set Pos 100%
OFF
Set Pos 0%
OFF
Set Dem 100%
OFF
Set Dem 0%
OFF
5F
RET Inhibitors
Balance
ON
Supervisory
OFF
Stall OFF
OverTrq/Thr
OFF
Switch Block
OFF
Bad Pos Sig
OFF
Bad Dem Sig
OFF
Local Cal
OFF
5G
EXT Inhibitors
Balance
ON
Supervisory
OFF
Stall OFF
OverTrq/Thr
OFF
Switch Block
OFF
Bad Pos Sig
OFF
Bad Dem Sig
OFF
Local Cal
OFF
5H
Alarm Mask
DemandLOS
ON
Trq/Thrust High
OFF
Stall ON
Trq/Thrust Stop
OFF
Stop/Limit
ON
FeedbackLOS
ON
Temperature
ON
PositionLOS
ON
RTC Fail
ON
Torq/Thrust/MeasFail OFF
PositionA/D Error
ON
DemandMeasFail ON
Reserved 1
ON
PositionLOS
ON
TemperatureMeasFail ON
MemoryFail
ON
InvalButtonPress ON
DemandTooHigh ON
DemUnderHART/FF Ctl ON
DemUnderPAT Ctl
ON
(3) PROVIDES AN EXTENDED LIST OF DRIVE PARAMETERS
Tests
1 FB Out Test**
2 Board Self-Test**
3 Identify Device**
4 Board Reset**
Configuration
1 General Setup
2 PositionSensrSetup
3 Demand Setup
4 Feedback Setup
5 Thrust Setup
6 Restore to Factory**
7 Use Default Setup**
Manual Operation
1 Op Mode*
Follow
2 Demand*
42.3%
3 Reset Stall**
BECK-MK2 HART DEVICE
DESCRIPTION (DD)
COMMUNICATOR MENUS
FOR THE DCM-3 (SHOWN
WITH SAMPLE VALUES)
INACTIVE
INACTIVE
INACTIVE
Содержание 14-100
Страница 85: ...85 80 1403 01 Rev 3 17 18 2 1 6 5 8 6 3 4 9 14 15 25 7 16 CONTROL ASSEMBLY AND DRIVE TRAIN...
Страница 87: ...87 80 1403 01 Rev 3 14 15 17 18 2 1 6 5 8 6 3 4 9 14 15 25 7 16 CONTROL ASSEMBLY AND DRIVE TRAIN...
Страница 90: ...90 80 1403 01 Rev 3 NOTES...
Страница 91: ...91 80 1403 01 Rev 3...