RAIN MODE 
 

 

 

SNOW MODE - 
STANDARD 

 

WIZARD SMR 
PROGRAMMING 
GUIDE – Cont. 
 

 

 
 
 
 
 

 
 
                                     
 

 
 
 
 
 
 

 
 
 
 
 

 
 
 

 

 
 
RAIN MODE: 

1.  The Rain Mode is designed to minimize the effect of heavy rain on the Wizard’s auto-learn 

requirements. Rain Mode will be enabled after the Wizard goes through two auto-learn cycles within 
no more than 6 detection cycles of the sensor between these 2 auto-learn cycles. During Rain Mode, 
auto-learn time will remain the same. However, the second infrared curtain will change from IR 
presence detection to IR motion detection. This is done to help eliminate unwanted detection of 
heavy rain, as well as it’s effects on the ground. The only required setting on the Wizard SMR to 
enable Rain Mode is IR Sensitivity, which must be set to a value of 2 (normal). This mode will 
automatically expire upon a power reset, or upon expiration of one hour. This mode could be 
launched again under the same conditions. 

 

 
 

STANDARD SNOW MODE: 

The Snow Mode is designed to minimize the effect of heavy snow on the Wizard’s auto-learn requirements. 
Snow Mode may only be enabled by performing the following: 
 

1. Using the BEA remote control, Unlock the Wizard as described in the programming guide. 
 

 
 

 

 

+ unlock code, if necessary. 

 
 

2. 

Set Infrared Sensitivity to LOW (1). 

 
 
 

 

 

+ 1 = Low Sensitivity 

 
 

3. 

Set Auto-Learn Time to 30 seconds (0). 

 
 

                        + 0 = 30 second learn-time 

 

 

 

 

 

 

 

 

 

 

 

 

 

4. 

Lock The Sensor when complete               +               

 
5.  After the above changes have been made, the Wizard will go into the Standard Snow Mode after it 

goes through 2 auto-learn cycles within no more than 6 detection cycles of the sensor between these 
2 auto-learn cycles. 

6. 

While  in  Standard  Snow  Mode,  the  auto-learn  time  will  change  from  30  seconds  to  10  seconds.                       
This mode will automatically expire upon a power reset, or upon expiration of one hour, as long as 
the settings (as outlined above) are in effect. This mode could be launched again under the same 
conditions. 

 

 

 

 
 
 
 

 
 
 
 

DOOR CONTROL 

FUNCTION 

The Door Control function enables the User 
to select a mode of door operation.  

1 = Door permanently open. 
2 = Door permanently closed – no 
detection 
3 = Door in automatic mode – 
Wizard, upon detection, opens door.

After pressing the DOOR CONTROL 
FUNCTION key, the red LED flashes 
quickly. After pressing a number 
button, the red LED flashes slowly.  

 IR CURTAIN 

The IR Curtain function allows the User to 
toggle the second IR curtain (farthest from 
the door) on & off. When the curtain is off, it 
operates in a motion sensing mode. 

1 = 1 IR curtain (inner) ON. 
2 = Both IR curtains (inner &  
      outer) ON. 

After pressing the IR CURTAIN 
FUNCTION key, the red LED flashes 
quickly. After pressing a number 
button, the red LED flashes slowly.  

IMPORTANT NOTE: 

When changing the values of the above parameters to go from one mode to another, one should 
force a set-up by remote control, push buttons, or by a power-off / on sequence. 

OBSOLETE

Содержание 10WIZARDC

Страница 1: ...250 g Housing material ABS LURAN S Color of Housing Anthracite gray standard aluminum or white finish Cable length 8 of six conductor cable MOTION SENSOR PRESENCE SENSOR Technology Microwave and micro...

Страница 2: ...ry for for all neagtive IR angles 3 Insert mounting screws about halfway in F shown on next page and install the Wizard onto the screws When in place tighten screws to secure to header Leave cover off...

Страница 3: ...Page 8 Wizards below SN 52000 will still require a 10IFBWIZARD Other Wiring Notes 1 When connecting to a microprocessed control box the Motion output and presence output wires may be connected to sepa...

Страница 4: ...tern being drawn back towards the door where as the 45 will place the pattern farther away Be certain to walk test detection field and insure compliance with current applicable ANSI standards 1 Insert...

Страница 5: ...bring the pattern nearer or farther from the face of the door by adjusting the tilt angle from 4 to 4 At the standard mounting height one complete clockwise turn of the adjustment screw will move the...

Страница 6: ...ng of 0 7 Default sensitivity value When all parameters have been set press the LOCK key once If you wish to enter a new access code use the 0 9 number keys and enter the new 4 digit code within 20 se...

Страница 7: ...y the red LED flashes quickly After pressing a number button the red LED flashes slowly IMMUNITY motion Immunity reduces the influence of unwanted disturbances within the field of motion detection wit...

Страница 8: ...conds 0 0 30 second learn time 4 Lock The Sensor when complete 5 After the above changes have been made the Wizard will go into the Standard Snow Mode after it goes through 2 auto learn cycles within...

Страница 9: ...ay be accomplished by the use of two Wizard mounted programming buttons The procedures below indicate how to program using these buttons The two set buttons are located at the right side of the Wizard...

Страница 10: ...y returns to standard mode if neither button has been pressed for one minute STEP 2 With all wiring in place apply power to door control and 12 to 24 VAC VDC 5 to 10 to Wizard Once powered observe LED...

Страница 11: ...ontrol or motor Refer to manufacturer s manual for further troubleshooting If door closes with sensor inputs removed fault exists with sensors or related wiring 1 On Off switch at door control in wron...

Страница 12: ...will not unlock when access code is entered 1 Improper code being entered 1 Reset code to the default value of 0000 by performing one of the following a Press the 2 buttons on the Wizard simultaneousl...

Страница 13: ...B 3 of the interface PH 412 249 4100 FAX 412 249 4101 B E A Inc 100 Enterprise Drive Pittsburgh PA 15275 REV 1 OF 1 NONE SIZE CAGE CODE DWG NO FILE OF GDM 20 MAR 2002 GDM A STANLEY DURAGLIDE WITH WIZA...

Страница 14: ...ZARD BROWN BLUE BLACK RED WHITE BROWN BLUE BLACK RED GREEN Reset 0 VDC Part open Exit Off 0 VDC Stop Impulse Pres Impulse 1 C Switch 0 v Pres Impulse 2 18 VDC 0 VDC Outer Impulse Inner Impulse 18 VDC...

Страница 15: ...MPULSE 24 VDC MONITORED SAFETY ONLY PHOTOCELL BESAM UNISLIDE SLIDING DOOR WITH WIZARD SYSTEM SIZE SHEET SCALE A PH 412 249 4100 FAX 412 249 4101 B E A Inc 100 Enterprise Drive Pittsburgh PA 15275 DATE...

Страница 16: ...ITCH PINS 5 6 7 LOOK SEE COM LINE PIN 8 LOOK SEE OUTPUT PINS 17 18 96010 900 QUANTUM SLIDE CONTROL BOX ACCESSORIES 24 VDC PIN 1 PIN 2 ACCESSORIES 24 VAC PINS 3 4 4 PIN 5 PIN EARTH GROUND NEUTRAL MAIN...

Отзывы: