POWER-UP
PROCEDURES
MANUAL SET-UP
(without remote)
MANUAL SET-UP
(without remote) –
Cont.
PARAMETER NUMBER
(altered by the right button and
confirmed by
GREEN LED
)
PARAMETER VALUES
(altered by the
left button and
confirmed by
RED LED
)
DEFAULT
VALUE
1 Radar
Sensitivity
0-9
7
2
Relay hold time
0-9
0
3 Output
configuration
1-6
4
4
Auto-learn
presence sensing
0-7 7
5 Detection
mode
1-4
3
6 Immunity
1-3
2
7 IR
sensitivity 1-2
1
8
Radar mounting
height
1-2 1
9
Not Used -
Must remain at 0
0 0
10
Door control function
1-3
3
11 SMR
mode 0-2
0
12 IR
curtain
1-2
2
EXAMPLE
: Change radar sensitivity from 7 to 9 and set hold time to 4 seconds:
1. Press the right button for 2 settings, you will enter the customizing mode
•
The green LED flashes once (parameter 1)
•
The red LED flashes 7 times (sensitivity = 7)
•
Press the left button twice to move from sensitivity = 7 to sensitivity = 9
2. Press the right button once to move to Parameter 2 (relay hold time)
•
The green LED flashes twice (parameter 2)
•
The red LED does not flash (hold time = 0 seconds)
•
Press the left button four times to move from hold time = 0 to hold time = 4 seconds
NOTE
:
1. When the highest value for the parameter has been reached, the value will “roll over” to its lowest value
(e.g. for radar mode: 1, 2, 3, then 1, 2, …).
2.
The sensor automatically returns to standard mode if neither button has been pressed for one minute.
STEP 2
With all wiring in place, apply power to door control
and 12 to 24 VAC / VDC: -5% to +10% to Wizard.
Once powered, observe LED status on the Wizard.
Stop all traffic through the doorway while
performing this step, and remain clear of the
Wizard’s detection zones.
STEP USER’S ACTION RESULT
The Wizard will flash a red / green LED during
the set-up procedure. Once the Wizard
completes set-up, the door will close and begin
normal operation thereafter.
STEP 1
Once set-up is complete, the LED indication will
reflect the status of the set-up. Observe the LED
while standing outside of the detection zones.
•
NO LED = Successful set-up
•
RED LED ON = Presence being detected -
Wizard is seeing an object.
•
RED LED Flashing for 10 seconds. Infrared
curtains are too close to door. Adjust curtains
using the Spotfinder.
•
GREEN LED MOMENTARILY ON = MOTION
DETECTION (Wizard sees movement).
•
ORANGE LED ON = Wizard is executing a
Self-Monitoring test (only when SMR mode is
enabled). LED should expire in approx. 6
seconds. If LED stays on, reset power and
observe LED. If it comes back on steady,
replace Wizard.
STEP 3
Proceed with fine tuning the mechanical , as well as
the program adjustments of the Wizard. Refer to the
applicable sections of this manual for altering any
settings. Be sure to check:
•
Motion width & depth
•
Presence width & depth
•
Position of infrared curtain
•
Sensitivity of motion field
Doors will always be adjusted to be in
compliance with ANSI A156.10