POWER-UP 
PROCEDURES  

 

MANUAL SET-UP 
(without remote) 

 

MANUAL SET-UP 
(without remote) – 
Cont. 

 

 
 

  
 

 
 
 
 

 

 

 
 
 

 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

PARAMETER NUMBER 

(altered by the right button and 

confirmed by 

GREEN LED

PARAMETER VALUES 

(altered by the 
left button and 

confirmed by 

RED LED

DEFAULT 

VALUE 

1 Radar 

Sensitivity 

0-9 

Relay hold time 

0-9 

3 Output 

configuration 

1-6 

Auto-learn  
presence sensing 

0-7 7 

5 Detection 

mode 

1-4 

6 Immunity 

1-3 

7 IR 

sensitivity  1-2 

Radar mounting 
height 

1-2 1 

Not Used - 
Must remain at 0 

0 0 

10 

Door control function 

1-3 

11 SMR 

mode  0-2 

12 IR 

curtain 

1-2 

EXAMPLE

:  Change radar sensitivity from 7 to 9 and set hold time to 4 seconds: 

1.   Press the right button for 2 settings, you will enter the customizing mode 

• 

The green LED flashes once (parameter 1) 

• 

The red LED flashes 7 times (sensitivity = 7) 

• 

Press the left button twice to move from sensitivity = 7 to sensitivity = 9 

 

2.   Press the right button once to move to Parameter 2 (relay hold time) 

• 

The green LED flashes twice (parameter 2) 

• 

The red LED does not flash (hold time = 0 seconds) 

• 

Press the left button four times to move from hold time = 0 to hold time = 4 seconds

 

 

NOTE

1.  When the highest value for the parameter has been reached, the value will “roll over” to its lowest value 

(e.g. for radar mode:  1, 2, 3, then 1, 2, …). 

2. 

The sensor automatically returns to standard mode if neither button has been pressed for one minute.

 

STEP 2 

With all wiring in place, apply power to door control 
and 12 to 24  VAC / VDC: -5%  to +10% to Wizard. 
Once powered, observe LED status on the Wizard. 
Stop all traffic through the doorway while 
performing this step, and remain clear of the 
Wizard’s detection zones. 
 

     

STEP                    USER’S ACTION                                                           RESULT 

The Wizard will flash a red / green LED during
the set-up procedure. Once the Wizard
completes set-up, the door will close and begin
normal operation thereafter. 

STEP 1 

Once set-up is complete, the LED indication will 
reflect the status of the set-up. Observe the LED 
while standing outside of the detection zones. 
 

• 

NO LED = Successful set-up 

• 

RED LED ON = Presence being detected -
Wizard is seeing an object. 

• 

RED LED Flashing for 10 seconds. Infrared
curtains are too close to door. Adjust curtains
using the Spotfinder. 

• 

GREEN LED MOMENTARILY ON = MOTION
DETECTION (Wizard sees movement). 

• 

ORANGE LED ON = Wizard is executing a
Self-Monitoring test (only when SMR mode is
enabled). LED should expire in approx. 6
seconds. If LED stays on, reset power and
observe LED. If it comes back on steady,
replace Wizard. 

STEP 3 

Proceed with fine tuning the mechanical , as well as 
the program adjustments of the Wizard. Refer to the 
applicable sections of this manual for altering any 
settings. Be sure to check: 

• 

Motion width & depth 

• 

Presence width & depth 

• 

Position of infrared curtain 

• 

Sensitivity of motion field 

Doors will always be adjusted to be in 
compliance with ANSI A156.10 

OBSOLETE

Содержание 10WIZARDC

Страница 1: ...250 g Housing material ABS LURAN S Color of Housing Anthracite gray standard aluminum or white finish Cable length 8 of six conductor cable MOTION SENSOR PRESENCE SENSOR Technology Microwave and micro...

Страница 2: ...ry for for all neagtive IR angles 3 Insert mounting screws about halfway in F shown on next page and install the Wizard onto the screws When in place tighten screws to secure to header Leave cover off...

Страница 3: ...Page 8 Wizards below SN 52000 will still require a 10IFBWIZARD Other Wiring Notes 1 When connecting to a microprocessed control box the Motion output and presence output wires may be connected to sepa...

Страница 4: ...tern being drawn back towards the door where as the 45 will place the pattern farther away Be certain to walk test detection field and insure compliance with current applicable ANSI standards 1 Insert...

Страница 5: ...bring the pattern nearer or farther from the face of the door by adjusting the tilt angle from 4 to 4 At the standard mounting height one complete clockwise turn of the adjustment screw will move the...

Страница 6: ...ng of 0 7 Default sensitivity value When all parameters have been set press the LOCK key once If you wish to enter a new access code use the 0 9 number keys and enter the new 4 digit code within 20 se...

Страница 7: ...y the red LED flashes quickly After pressing a number button the red LED flashes slowly IMMUNITY motion Immunity reduces the influence of unwanted disturbances within the field of motion detection wit...

Страница 8: ...conds 0 0 30 second learn time 4 Lock The Sensor when complete 5 After the above changes have been made the Wizard will go into the Standard Snow Mode after it goes through 2 auto learn cycles within...

Страница 9: ...ay be accomplished by the use of two Wizard mounted programming buttons The procedures below indicate how to program using these buttons The two set buttons are located at the right side of the Wizard...

Страница 10: ...y returns to standard mode if neither button has been pressed for one minute STEP 2 With all wiring in place apply power to door control and 12 to 24 VAC VDC 5 to 10 to Wizard Once powered observe LED...

Страница 11: ...ontrol or motor Refer to manufacturer s manual for further troubleshooting If door closes with sensor inputs removed fault exists with sensors or related wiring 1 On Off switch at door control in wron...

Страница 12: ...will not unlock when access code is entered 1 Improper code being entered 1 Reset code to the default value of 0000 by performing one of the following a Press the 2 buttons on the Wizard simultaneousl...

Страница 13: ...B 3 of the interface PH 412 249 4100 FAX 412 249 4101 B E A Inc 100 Enterprise Drive Pittsburgh PA 15275 REV 1 OF 1 NONE SIZE CAGE CODE DWG NO FILE OF GDM 20 MAR 2002 GDM A STANLEY DURAGLIDE WITH WIZA...

Страница 14: ...ZARD BROWN BLUE BLACK RED WHITE BROWN BLUE BLACK RED GREEN Reset 0 VDC Part open Exit Off 0 VDC Stop Impulse Pres Impulse 1 C Switch 0 v Pres Impulse 2 18 VDC 0 VDC Outer Impulse Inner Impulse 18 VDC...

Страница 15: ...MPULSE 24 VDC MONITORED SAFETY ONLY PHOTOCELL BESAM UNISLIDE SLIDING DOOR WITH WIZARD SYSTEM SIZE SHEET SCALE A PH 412 249 4100 FAX 412 249 4101 B E A Inc 100 Enterprise Drive Pittsburgh PA 15275 DATE...

Страница 16: ...ITCH PINS 5 6 7 LOOK SEE COM LINE PIN 8 LOOK SEE OUTPUT PINS 17 18 96010 900 QUANTUM SLIDE CONTROL BOX ACCESSORIES 24 VDC PIN 1 PIN 2 ACCESSORIES 24 VAC PINS 3 4 4 PIN 5 PIN EARTH GROUND NEUTRAL MAIN...

Отзывы: